@inproceedings{KernDikta2009, author = {Kern, Alexander and Dikta, Gerhard}, title = {Probability of damage of electrical and electronic systems due to indirect lightning flashes - investigation of data from German insurance companies}, year = {2009}, abstract = {In the presented paper data collected from the field related to damage statistics of electrical and electronic apparatus in household are reported and investigated. These damages (total number approx. 74000 cases), registered by five German insurance companies in 2005 and 2006, were adviced by customers as caused by lightning overvoltages. With the use of stochastical methods it is possible, to reasses the collected data and to distinguish between cases, which are with high probability caused by lightning overvoltages, and those, which are not. If there was an indication for a direct strike, this case was excluded, so the focus was only on indirect lightning flashes, i.e. only flashes to ground near the structure and flashes to or nearby an incoming service line were investigated. The data from the field contain the location of damaged apparatus (residence of the policy holder) and the distances of the nearest cloud-to-ground stroke to the location of the damage registered by the German lightning location network BLIDS at the date of damage. The statistical data along with some complementary numerical simulations allow to verify the correspondence of the Standards rules used for IEC 62305-2 with the field data and to define some correction needs. The results could lead to a better understanding whether a damage reported to an insurance company is really caused by indirect lightning, or not.}, subject = {Blitzschutz}, language = {en} } @inproceedings{KernBeierlZischank2009, author = {Kern, Alexander and Beierl, Ottmar and Zischank, Wolfgang}, title = {Calculation of the separation distance according to IEC 62305-3: 2006-10 - Remarks for the application and simplified methods}, year = {2009}, abstract = {[Paper of the X International Symposium on Lightning Protection 9th - 13th November, 2009 - Curitiba, Brazil. 6 pages] The international standard IEC 62305-3, published in 2006, requires as an integral part of the lightning protection system (LPS) the consideration of a separation distance between the conductors of the LPS and metal and electrical installations inside the structure to be protected. IEC 62305-3 gives two different methods for this calculation: a standard, simplified approach and a more detailed approach, which differ especially regarding the treatment of the current sharing effect on the LPS conductors. Hence, different results for the separation distance are possible, leading to some discrepancies in the use of the standard. The standard approach defined in the main part (Clause 6.3) and in Annex C of the standard in some cases may lead to a severe oversizing of the required separation distance. The detailed approach described in Annex E naturally gives more correct results. However, a calculation of the current sharing amongst all parts of the air-termination and downconductor network is necessary, in many cases requiring the use of network analysis programs. In this paper simplified methods for the assessment of the current sharing are presented, which are easy to use as well as sufficiently adequate.}, subject = {Blitzschutz}, language = {de} } @inproceedings{BehrensFrentzelKern2009, author = {Behrens, J{\"o}rg and Frentzel, Ralf and Kern, Alexander}, title = {Simulation der transienten Spannungsverl{\"a}ufe im Eigenbedarfsnetz eines Großkraftwerks bei einem kraftwerksnahen Blitzeinschlag in die Hochspannungs-Freileitung}, isbn = {978-3-8007-3197-8}, year = {2009}, abstract = {8. VDE/ABB-Blitzschutztagung, 29. - 30. Oktober 2009 in Neu-Ulm. Blitzschutztagung <8, 2009, Neu-Ulm> Berlin : VDE Verl. 2009 Großkraftwerke k{\"o}nnen durch Blitzentladungen mit potentiellen Auswirkungen auf deren Verf{\"u}gbarkeit und Sicherheit gef{\"a}hrdet werden. Ein sehr spezielles Szenario, welches aus aktuellem Anlass zu untersuchen war, betrifft den kraftwerksnahen Blitzeinschlag in die Hochspannungs-Freileitung am Netzanschluss der Anlage. Wird nun noch ein sogenannter Schirmfehler unterstellt, d.h. der direkte Blitzeinschlag erfolgt in ein Leiterseil des Hoch- bzw. H{\"o}chstspannungsnetzes und nicht in das dar{\"u}ber gespannte Erdseil, so bedeutet dies eine extreme elektromagnetische Einwirkung. Der vorliegende Beitrag befasst sich mit der Simulation eines solchen Blitzeinschlages und dessen Auswirkungen auf den Netzanschluss und die Komponenten der elektrischen Eigenbedarfsanlagen eines Kraftwerks auf den unterlagerten Spannungsebenen. Die dabei gewonnenen Erkenntnisse lassen sich ohne Einschr{\"a}nkungen auf Industrieanlagen mit Mittelspannungs-Netzanschluss und ohne eigener Stromversorgung {\"u}bertragen.}, subject = {Blitzschutz}, language = {de} } @inproceedings{Kern2013, author = {Kern, Alexander}, title = {Die neue DIN EN 62305-2 (VDE 0185-305-2) Ed.2:2013-02 - {\"A}nderungen zur Ed.l und zugeh{\"o}rige Beibl{\"a}tter}, series = {10. VDE, VBB-Blitzschutztagung : Vortr{\"a}ge der 10. VDE, ABB-Fachtagung vom 24. bis 25. Oktober 2013 in Neu-Ulm. (VDE-Fachbericht ; 70)}, booktitle = {10. VDE, VBB-Blitzschutztagung : Vortr{\"a}ge der 10. VDE, ABB-Fachtagung vom 24. bis 25. Oktober 2013 in Neu-Ulm. (VDE-Fachbericht ; 70)}, publisher = {VDE-Verl.}, address = {Berlin}, organization = {Blitzschutztagung <10, 2013, Neu-Ulm>}, isbn = {978-3-8007-3540-2}, pages = {9 -- 16}, year = {2013}, language = {de} } @inproceedings{ScheibeKern2013, author = {Scheibe, K. and Kern, Alexander}, title = {Stand der Normung f{\"u}r {\"U}berspannungsschutzger{\"a}te}, series = {10. VDE, VBB-Blitzschutztagung : Vortr{\"a}ge der 10. VDE, ABB-Fachtagung vom 24. bis 25. Oktober 2013 in Neu-Ulm. (VDE-Fachbericht ; 70)}, booktitle = {10. VDE, VBB-Blitzschutztagung : Vortr{\"a}ge der 10. VDE, ABB-Fachtagung vom 24. bis 25. Oktober 2013 in Neu-Ulm. (VDE-Fachbericht ; 70)}, publisher = {VDE-Verl.}, address = {Berlin}, organization = {Blitzschutztagung <10, 2013, Neu-Ulm>}, isbn = {978-3-8007-3540-2}, pages = {23 -- 27}, year = {2013}, language = {de} } @inproceedings{WetterKern2014, author = {Wetter, Martin and Kern, Alexander}, title = {Number of lightning strikes to tall structures - comparison of calculations and measurements using a modern lightning monitoring system}, series = {2014 International Conference on Lightning Protection (ICLP), Shanghai, China}, booktitle = {2014 International Conference on Lightning Protection (ICLP), Shanghai, China}, organization = {International Conference on Lightning Protection <2014, Shanghai>}, pages = {1 -- 7}, year = {2014}, language = {en} } @inproceedings{KernSchelthoffMathieu2012, author = {Kern, Alexander and Schelthoff, Christof and Mathieu, Moritz}, title = {Calculation of interception efficiencies for mesh-type air-terminations according to IEC 62305-3 using a dynamic electro-geometrical model}, series = {International Conference on Lightning Protection (ICLP) : 2 - 7 Sept. 2012, Vienna}, booktitle = {International Conference on Lightning Protection (ICLP) : 2 - 7 Sept. 2012, Vienna}, publisher = {IEEE}, address = {Piscataway, NJ}, organization = {International Conference on Lightning Protection <2012, Wien>}, isbn = {978-1-4673-1896-9 (E-Book) ; 978-1-4673-1898-3 (Print)}, pages = {1 -- 6}, year = {2012}, language = {en} } @inproceedings{LoPiparoKernMazzetti2012, author = {Lo Piparo, G. B. and Kern, Alexander and Mazzetti, C.}, title = {Some masterpoints about risk due to lightning}, series = {International Conference on Lightning Protection (ICLP) : 2 - 7 Sept. 2012, Vienna}, booktitle = {International Conference on Lightning Protection (ICLP) : 2 - 7 Sept. 2012, Vienna}, publisher = {IEEE}, address = {Piscataway, NJ}, organization = {International Conference on Lightning Protection <2012, Wien>}, isbn = {978-1-4673-1896-9 (E-Book) ; 978-1-4673-1898-3 (Print)}, pages = {1 -- 6}, year = {2012}, language = {en} } @inproceedings{RousseauKern2014, author = {Rousseau, Alain and Kern, Alexander}, title = {How to deal with environmental risk in IEC 62305-2}, series = {2014 International Conference on Lightning Protection (ICLP), Shanghai, China}, booktitle = {2014 International Conference on Lightning Protection (ICLP), Shanghai, China}, organization = {International Conference on Lightning Protection <2014, Shanghai>}, pages = {521 -- 527}, year = {2014}, abstract = {The 2nd edition of the lightning risk management standard (IEC 62305-2) considers structures, which may endanger environment. In these cases, the loss is not limited to the structure itself, which is valid for usual structures. In the past (Edition 1) this danger was simply taken into account by a special hazard factor, multiplying the existing risk for the structure with a number. Now, in the edition 2, we add to the risk for the structure itself a "second risk" due to the losses outside the structure. The losses outside can be treated independently from what occurs inside. This is a major advantage to analyze the risk for sensitive structures, like chemical plants, nuclear plants, or structures containing explosives, etc. In this paper, the existing procedure given by the European version EN 62305-2 Ed.2 is further developed and applied to a few structures.}, language = {en} } @inproceedings{KernBraun2014, author = {Kern, Alexander and Braun, Christian}, title = {Risk management according to IEC 62305-2 edition 2: 2010-12 assessment of structures with a risk of explosion}, series = {2014 International Conference on Lightning Protection (ICLP), Shanghai, China}, booktitle = {2014 International Conference on Lightning Protection (ICLP), Shanghai, China}, organization = {International Conference on Lightning Protection <2014, Shanghai>}, pages = {1237 -- 1242}, year = {2014}, abstract = {Risk management for structures with a risk of explosion should be considered very carefully when performing a risk analysis according to IEC 62305-2. In contrast to the 2006 edition of the standard, the 2010 edition describes the topic "Structures with a risk of explosion" in more detail. Moreover, in Germany separate procedures and parameters are defined for the risk analysis of structures with a risk of explosion (Supplement 3 of the German DIN EN 62305-2 standard). This paper describes the contents and the relevant calculations of this Supplement 3, together with a numerical example.}, language = {en} }