@inproceedings{ZischankKernFrentzeletal.2000, author = {Zischank, Wolfgang J. and Kern, Alexander and Frentzel, Ralf and Heidler, Fridolin and Seevers, M.}, title = {Assessment of the lightning transient coupling to control cables interconnecting structures in large industrial facilities and power plants}, year = {2000}, abstract = {Large industrial facilities and power plants often require a huge number fo information and control cables between the differnet structures. These I\&C-cables can be routed in reinforced concrete cable ducts or in isolated buried cable runs. KTA 2206 is the German lightning protection standard for nuclear power plants. During the last several years considerable effort has been made to revise this standard. Despite the well established principles and design guidelines for the construction of the lightning protection system, this standard puts special emphasis on the coupling of transient overvoltages to I\&C-cables.}, language = {en} } @inproceedings{KernBeierlZischank2009, author = {Kern, Alexander and Beierl, Ottmar and Zischank, Wolfgang}, title = {Calculation of the separation distance according to IEC 62305-3: 2006-10 - Remarks for the application and simplified methods}, year = {2009}, abstract = {[Paper of the X International Symposium on Lightning Protection 9th - 13th November, 2009 - Curitiba, Brazil. 6 pages] The international standard IEC 62305-3, published in 2006, requires as an integral part of the lightning protection system (LPS) the consideration of a separation distance between the conductors of the LPS and metal and electrical installations inside the structure to be protected. IEC 62305-3 gives two different methods for this calculation: a standard, simplified approach and a more detailed approach, which differ especially regarding the treatment of the current sharing effect on the LPS conductors. Hence, different results for the separation distance are possible, leading to some discrepancies in the use of the standard. The standard approach defined in the main part (Clause 6.3) and in Annex C of the standard in some cases may lead to a severe oversizing of the required separation distance. The detailed approach described in Annex E naturally gives more correct results. However, a calculation of the current sharing amongst all parts of the air-termination and downconductor network is necessary, in many cases requiring the use of network analysis programs. In this paper simplified methods for the assessment of the current sharing are presented, which are easy to use as well as sufficiently adequate.}, subject = {Blitzschutz}, language = {de} }