TY - CHAP A1 - Kern, Alexander A1 - Imani Vashiani, Anahita A1 - Timmermanns, Tobias T1 - Threat for human beings due to touch voltages and body currents caused by direct lightning strikes in case of non-isolated lightning protection systems using natural components T2 - 35th International Conference on Lightning Protection (ICLP) and XVI International Symposium on Lightning Protection (SIPDA) N2 - For typical cases of non-isolated lightning protection systems (LPS) the impulse currents are investigated which may flow through a human body directly touching a structural part of the LPS. Based on a basic LPS model with conventional down-conductors especially the cases of external and internal steel columns and metal façades are considered and compared. Numerical simulations of the line quantities voltages and currents in the time domain are performed with an equivalent circuit of the entire LPS. As a result it can be stated that by increasing the number of conventional down-conductors and external steel columns the threat for a human being can indeed be reduced, but not down to an acceptable limit. In case of internal steel columns used as natural down-conductors the threat can be reduced sufficiently, depending on the low-resistive connection of the steel columns to the lightning equipotential bonding or the earth termination system, resp. If a metal façade is used the threat for human beings touching is usually very low, if the façade is sufficiently interconnected and multiply connected to the lightning equipotential bonding or the earth termination system, resp. KW - Lightning protection system KW - down-conductor KW - steel columns KW - metal façade KW - touch voltage Y1 - 2021 SN - 978-1-6654-2346-5 U6 - http://dx.doi.org/10.1109/ICLPandSIPDA54065.2021.9627465 N1 - 35th International Conference on Lightning Protection (ICLP) and XVI International Symposium on Lightning Protection (SIPDA), 20-26 Sept. 2021, Colombo, Sri Lanka PB - IEEE ER - TY - CHAP A1 - Birkl, Josef A1 - Diendorfer, Gerhard A1 - Kern, Alexander A1 - Thern, Stephan T1 - Extremely high lightning peak currents T2 - 34th International Conference on Ligntning Protection, 02-07 September 2018 Y1 - 2018 SN - 978-1-5386-6635-7 ER - TY - JOUR A1 - Birkl, Josef A1 - Diendorfer, Gerhard A1 - Kern, Alexander A1 - Thern, Stephan T1 - Extrem hohe Blitzströme JF - Elektropraktiker N2 - Blitze sind nach wie vor eine enorme Schadensquelle für Personenschäden, Brände, mechanische Zerstörungen und insbesondere auch Überspannungen. Das zeigen nicht zuletzt aktuelle Statistiken der Schadensversicherer. Immer wieder gibt es Meldungen über extrem hohe Blitzströme, die natürlich auch zu großen Schäden und Zerstörungen führen können. Dabei werden Scheitelwerte von teilweise deutlich über 300 kA genannt. Dies wirft Fragen auf, da die „klassische“ Blitzstatistik (z. B. nach CIGRE und IEC [8][10]) bisher solche Werte nicht kennt. Diese extremen Blitzströme werden meist aus den Daten von Blitzortungssystemen ermittelt. Y1 - 2018 VL - 72 IS - 3 SP - 217 EP - 225 PB - Huss Medien CY - Berlin ER - TY - CHAP A1 - Kern, Alexander T1 - Optimierung des Blitzschutzes bei Biogasanlagen T1 - Improvement of lightning protection for biogas plants T2 - 12. VDE/ABB-Blitzschutztagung : Beiträge der 12. VDE/ABB-Fachtagung, 12.-13. Oktober 2017, Aschaffenburg Y1 - 2017 SN - 978-3-8007-4459-6 SP - 48 EP - 56 ER - TY - CHAP A1 - Kern, Alexander A1 - Brocke, Ralph T1 - Planung von Fangeinrichtungen mit dem dynamischen elektro-geometrischen Modell - Mögliche praktische Anwendungen T1 - Design of air-terminations using the dynamic electro-geometrical model - Possible practical applications T2 - 12. VDE/ABB-Blitzschutztagung : Beiträge der 12. VDE/ABB-Fachtagung, 12.-13. Oktober 2017, Aschaffenburg Y1 - 2017 SN - 978-3-8007-4459-6 SP - 75 EP - 82 ER - TY - CHAP A1 - Birkl, Josef A1 - Diendorfer, Gerhard A1 - Kern, Alexander A1 - Thern, Stephan T1 - Extrem hohe Blitzströme T1 - Extremly high lightning currents T2 - 12. VDE/ABB-Blitzschutztagung : Beiträge der 12. VDE/ABB-Fachtagung, 12.-13. Oktober 2017, Aschaffenburg Y1 - 2017 SN - 978-3-8007-4459-6 SP - 146 EP - 152 ER - TY - JOUR A1 - Kern, Alexander T1 - Blitz- und Überspannungsschutz von Kernkraftwerken - Nachweisführung der ausreichenden Sicherheit für leittechnische Einrichtungen auch bei Blitzeinschlägen mit extremen Parametern JF - Atw. International Journal for Nuclear Power N2 - Für das Auftreten extremer Wetterereignisse werden für Kernkraftwerke Eintrittshäufigkeiten für nicht mehr beherrschbare Zustände von unter 10⁻⁴/a gefordert. Dies gilt auch für die Einwirkung von Blitzeinschlägen. Die bisherige Nachweisführung zu Blitz- und Überspannungsschutz eines KKW in Deutschland ist deterministisch. In diesem Bericht werden das Vorgehen für einen entsprechenden Nachweis für leittechnische Einrichtungen der Sicherheitstechnik von KKW, der zur geforderten Zielgröße der Eintrittshäufigkeit führt. Die Ergebnisse werden zusammenfassend bewertet. Y1 - 2016 SN - 1431-5254 VL - 61 IS - 8/9 SP - 534 EP - 543 PB - Inforum CY - Berlin ER - TY - BOOK A1 - Kern, Alexander A1 - Wettingfeld, Jürgen T1 - Blitzschutzsysteme 2 : Schutz für besondere bauliche Anlagen ; Schutz für elektrische und elektronische Systeme in baulichen Anlagen ; Erläuterungen zu den Normen DIN EN 62305-3 (VDE 0185-305-3):2011-10, DIN EN 62305-4 (VDE 0185-305-4):2011-10. (VDE-Schriftenreihe Normen verständlich ; 160) Y1 - 2015 SN - 978-3-8007-3653-9 PB - VDE-Verl. CY - Berlin [u.a.] ER - TY - CHAP A1 - Wetter, Martin A1 - Kern, Alexander T1 - Number of lightning strikes to tall structures - comparison of calculations and measurements using a modern lightning monitoring system T2 - 2014 International Conference on Lightning Protection (ICLP), Shanghai, China Y1 - 2014 SP - 1 EP - 7 ER - TY - BOOK A1 - Kern, Alexander A1 - Wettingfeld, Jürgen T1 - Blitzschutzsysteme 1 : allgemeine Grundsätze, Risikomanagement, Schutz von baulichen Anlagen und Personen ; Erläuterungen zu den Normen DIN EN 62305-1 (VDE 0185-305-1):2011-10, DIN EN 62305-2 (VDE 0185-305-2):2013-02, DIN EN 62305-3 (VDE 0185-305-3):2011-10. (VDE-Schriftenreihe Normen verständlich ; 44) Y1 - 2014 SN - 978-3-8007-3511-2 PB - VDE-Verl. CY - Berlin [u.a.] ER -