TY - JOUR A1 - Kern, Alexander A1 - Zischank, Wolfgang J. T1 - Melting effects on metal sheets and air termination wires caused by direct lightning strikes JF - Conference proceedings : Graz, Österreich, 25. - 29. April 1988 / Gesamtorganisation: Österr. Verb. für Elektrotechnik (ÖVE), Fachausschuß Blitzschutz ... [Red.: G. Diendorfer ...] Y1 - 1988 SN - 3-85133-001-3 N1 - International Conference on Lightning Protection >19, 1988, Graz> ; ICLP <19, 1988, Graz> ; Österreichischer Verband für Elektrotechnik / Fachausschuss Blitzschutz PB - Eigenverl. des ÖVE CY - Wien ER - TY - JOUR A1 - Kern, Alexander T1 - Time dependent temperature distribution in metal sheets caused by direct lightning strikes JF - Proceedings / Sixth International Symposium on High Voltage Engineering : 28. August - 1. September, 1989, Westin Canal Place Hotel, New Orleans, Louisiana, USA Y1 - 1989 N1 - International Symposium on High Voltage Engineering <6, 1989, New Orleans, La.> PB - Mississippi State University CY - Mississippi State, Miss. ER - TY - JOUR A1 - Kern, Alexander A1 - Lang, U. A1 - Wiesinger, J. A1 - Zischank, Wolfgang J. T1 - The longitudinal voltage of cable tubes with a screening mesh caused by partial lightning currents JF - Proceedings / Sixth International Symposium on High Voltage Engineering : 28. August - 1. September, 1989, Westin Canal Place Hotel, New Orleans, Louisiana, USA Y1 - 1989 N1 - International Symposium on High Voltage Engineering <6, 1989, New Orleans, La.> PB - Mississippi State University CY - Mississippi State, Miss. ER - TY - JOUR A1 - Kern, Alexander T1 - The heating of metal sheets caused by direct lightning strikes-model and measurement JF - 20th ICPL / International Conference on Lightning Protection, Congress-Center Casino Interlaken, Switzerland, September 24-28, 1990 = Internationale Blitzschutzkonferenz, Congress-Center Casino Interlaken, Schweiz, 24.-28. September 1990 Y1 - 1990 N1 - International Conference on Lightning Protection <20, 1990, Interlaken> ; Internationale Blitzschutzkonferenz <20, 1990, Interlaken> PB - Schweizerischer Elektrotechnischer Verein CY - [Zürich] ER - TY - BOOK A1 - Kern, Alexander T1 - Theoretische und experimentelle Untersuchung der Erwärmung von Metallblechen bei Blitzeinschlag Y1 - 1990 N1 - Diss. PB - Univ. der Bundeswehr CY - München ER - TY - JOUR A1 - Kern, Alexander A1 - Wiesinger, J. A1 - Zischank, Wolfgang J. T1 - Calculation of the longitudinal voltage along metal tubes caused by lightning currents and protection measures JF - Seventh International Symposium on High Voltage Engineering : Dresden, August 26 - 30 1991 Y1 - 1991 N1 - International Symposium on High Voltage Engineering <7, 1991, Dresden> PB - Techn. Univ. CY - Dresden ER - TY - JOUR A1 - Kern, Alexander T1 - Simulation and measurement of melting effects on metal sheets caused by direct lightning strikes JF - 1991 International Aerospace and Ground Conference on Lightning and Static Electricity : proceedings of a conference ... held at Cocoa Beach, Florida, April 16-19, 1991 / NASA Y1 - 1991 N1 - International Aerospace and Ground Conference on Lightning and Static Electricity <1991, Cocoa Beach, Fla.> ; United States / National Aeronautics and Space Administration CY - Washington, DC ER - TY - JOUR A1 - Kern, Alexander A1 - Hasse, P. A1 - Wiesinger, J. A1 - Zischank, Wolfgang J. T1 - Aktuelles aus der Blitzforschung JF - ETZ : Elektrotechnik + Automation. 112 (1991), H. 1 Y1 - 1991 SN - 0170-1711 N1 - 2. ISSN: 0948-7387 ER - TY - JOUR A1 - Kern, Alexander A1 - Roth, J. A1 - Wiedmann, J. T1 - Comparison of the damage for various types of fibre reinforced composites due to different lightning test standards (MIL-STD 1757 A, German military VG-standard 96903) JF - Proceedings of the 1992 International Aerospace and Ground Conference on Lightning and Static Electricity : October 6-8, 1992, Trump Taj Mahal, Atlantic City, NJ. Y1 - 1992 N1 - International Conference on Lightning and Static Electricity <1992, Atlantic City, NJ> PB - U.S. Dept. of Transportation, Federal Aviation Administration CY - [Atlantic City, N.J.] ER - TY - JOUR A1 - Kern, Alexander A1 - Zischank, Wolfgang J. T1 - The effect of parallel wires on the longitudinal voltage drop along shielded cables JF - Conference proceedings : 21st International Conference on Lightning Protection, Berlin Congress Center (BCC) Germany, September 22 - 25, 1992 = 21. Internationale Blitzschutzkonferenz / [proceedings ed. staff: J. Pilling ...] Y1 - 1992 SN - 3-8007-1885-5 N1 - International Conference on Lightning Protection <21, 1992, Berlin> ; ICLP <21, 1992, Berlin> PB - VDE-Verl. CY - Berlin [u.a.] ER - TY - JOUR A1 - Kern, Alexander A1 - Zischank, Wolfgang J. T1 - Längsspannung an blitzstromdurchflossenen Schirmkabeln - Einfluß paralleler Entlastungsleitungen JF - Elektrie : wissenschaftlich-technische Zeitschrift der Elektrotechnik. 47 (1993), H. 6 Y1 - 1993 SN - 0013-5399 N1 - 2. ISSN: 0013-5400 ER - TY - JOUR A1 - Kern, Alexander A1 - Heidler, Fridolin A1 - Zahlmann, P. A1 - Zischank, Wolfgang J. T1 - Blitzschutz JF - ETZ : Elektrotechnik + Automation. 114 (1993), H. 2 Y1 - 1993 SN - 0170-1711 N1 - 2. ISSN: 0948-7387 ER - TY - JOUR A1 - Kern, Alexander T1 - Physik der Blitzentladung und Blitzstrom-Parameter bei natürlichen Blitzen Y1 - 1993 N1 - Wehrtechnisches Symposium Elektromagnetische Verträglichkeit <5, 1993, Mannheim> ER - TY - JOUR A1 - Kern, Alexander A1 - Thomsen, M. T1 - Comparison of single point and equipotential bonding for I&C systems of large-area industrial sites JF - Volume of proceedings : Budapest, Hungary, September 19-23, 1994 / organized by: Technical University of Budapest Y1 - 1994 N1 - International Conference on Lightning Protection <22, 1994, Budapest> ; ICLP <22, 1994, Budapest> ; Budapesti Műszaki Egyetem PB - Techn. Univ. CY - Budapest ER - TY - JOUR A1 - Kern, Alexander A1 - Drumm, F. T1 - Survey of the lightning threat for aircraft based on natural lightning data and fixed in the German Standard DIN VG 95371 / Part 10 JF - Proceedings of the 1994 International Aerospace and Ground Conference on Lightning and Static Electricity : May 14 - 27, 1994, Bundesakademie für Wehrverwaltung und Wehrtechnik Mannheim ; final report / [conference chairman Jan Luiken TerHaseborg] Y1 - 1994 N1 - International Aerospace and Ground Conference on Lightning and Static Electricity <16, 1994, Mannheim> PB - Bundesakad. für Wehrverwaltung und Wehrtechnik CY - Mannheim ER - TY - JOUR A1 - Kern, Alexander A1 - Kaiser, Ludwig T1 - Auswirkungen des EMVG auf leittechnische Einrichtungen in großflächigen Industrieanlagen / von Ludwig Kaiser ; Alexander Kern JF - ETZ : Elektrotechnik + Automation. 116 (1995), H. 9 Y1 - 1995 SN - 0170-1711 N1 - 2. ISSN: 0948-7387 ; In der Bibliothek unter 23 Z 133 (Eupener Str.) und 63 ZS 035 (Jülich) vorhanden. SP - 16 EP - 18 ER - TY - JOUR A1 - Kern, Alexander T1 - Blitz-Störschutz als Maßnahme der EMV am Beispiel einer ausgedehnten Industrieanlage Y1 - 1995 N1 - Forum für Sachverständige, Fa. Dehn + Söhne <2, 1995, Nürnberg> ER - TY - JOUR A1 - Kern, Alexander T1 - Blitz-Schutzzonen mit Schirmungen und Schnittstellen JF - Blitzschutz für Gebäude und elektrische Anlagen : Vorträge der VDE/ABB-Fachtagung am 29. Februar und 1. März 1996 in Kassel / Veranst.: Ausschuß Blitzschutz und Blitzforschung (ABB) im VDE-Verband Dt. Elektrotechniker e.V. Wiss. Tagungsleit.: F. Noack. - (Verband Deutscher Elektrotechniker: VDE-Fachbericht ; 49) Y1 - 1996 SN - 3-8007-2161-9 N1 - Blitzschutztagung <1, 1996, Kassel> ; Verband Deutscher Elektrotechniker / Ausschuss für Blitzschutz und Blitzforschung PB - VDE-Verl. CY - Berlin [u.a.] ER - TY - JOUR A1 - Kern, Alexander A1 - Zischank, Wolfgang J. A1 - Heidler, Fridolin A1 - Wiesinger, J. [u.a.] T1 - Shielding effectiveness of reinforced concrete cable ducts carrying partial lightning currents JF - Conference proceedings : 14th - 18th September 1998, [Burlington Hotel, Birmingham, United Kingdom] / organised by: School of Engineering and Advanced Technology, Staffordshire University, United Kingdom Y1 - 1998 N1 - International Conference on Lightning Protection <24, 1998, Birmingham> ; School of Engineering and Advanced Technology ; ICLP <4, 1998, Birmingham> CY - Birmingham ER - TY - JOUR A1 - Kern, Alexander T1 - Beispiele für EMV-Maßnahmen in großflächigen Anlagen JF - EMV von Gebäuden, Anlagen und Geräten : praktische Umsetzung der technischen, wirtschaftlichen und gesetzlichen Anforderungen für die CE-Kennzeichnung / Anton Kohling (Hrsg.). Gerd Balzer... Y1 - 1998 SN - 3-8007-2261-5 PB - VDE-Verl. CY - Berlin [u.a.] ER - TY - JOUR A1 - Kern, Alexander T1 - Ertüchtigung des Blitzschutzsystems für ein Bürogebäude auf der Basis von VDE V 0185 Teil 100 (ENV 61024-1) und VDE 0185 Teil 103 (IEC 1312-1) Y1 - 1998 N1 - Forum Verband Deutscher Blitzschutzfirmen e.V. <1998, Köln> ER - TY - JOUR A1 - Kern, Alexander A1 - Heidler, F. A1 - Zischank, W. T1 - Induced overvoltages in cable ducts taking into account the current flow into earth / F. Heidler ; W. Zischank ... A. Kern ... JF - Conference proceedings : 14th - 18th September 1998, [Burlington Hotel, Birmingham, United Kingdom] / organised by: School of Engineering and Advanced Technology, Staffordshire University, United Kingdom Y1 - 1998 N1 - International Conference on Lightning Protection <24, 1998, Birmingham> ; School of Engineering and Advanced Technology ; ICLP <4, 1998, Birmingham> CY - Birmingham ER - TY - JOUR A1 - Kern, Alexander T1 - Aktueller Stand zu Risikoabschätzungen bei Blitzeinschlägen - Was ist neu in der IEC 61662 Edition 2? Y1 - 2000 N1 - Forum Verband Deutscher Blitzschutzfirmen e.V. <2000, Köln> ER - TY - CHAP A1 - Zischank, Wolfgang J. A1 - Kern, Alexander A1 - Frentzel, Ralf A1 - Heidler, Fridolin A1 - Seevers, M. T1 - Assessment of the lightning transient coupling to control cables interconnecting structures in large industrial facilities and power plants N2 - Large industrial facilities and power plants often require a huge number fo information and control cables between the differnet structures. These I&C-cables can be routed in reinforced concrete cable ducts or in isolated buried cable runs. KTA 2206 is the German lightning protection standard for nuclear power plants. During the last several years considerable effort has been made to revise this standard. Despite the well established principles and design guidelines for the construction of the lightning protection system, this standard puts special emphasis on the coupling of transient overvoltages to I&C-cables. KW - Blitzschutz KW - Elektromagnetische Kopplung KW - Überspannung KW - Kraftwerke KW - Industrieanlagen KW - Lightning KW - current distribution KW - electromagnetic coupling KW - overvoltages Y1 - 2000 ER - TY - JOUR A1 - Kern, Alexander A1 - Krichel, Frank A1 - Neskakis, Apostolos A1 - Müller, Klaus-Peter (u.a.) T1 - Lightning protection design of a renewable energy hybrid-system without power mains connection Y1 - 2001 N1 - International Conference on Renewable Energies for Islands <2001, Crete> ER - TY - CHAP A1 - Kern, Alexander A1 - Meppelink, Jan T1 - Neue Möglichkeiten elektrischer Anschlüsse an die Bewehrung und Untersuchung der Wirkung von Blitzströmen in bewehrtem Beton N2 - Im Rahmen eines modernen Blitzschutzsystems für Stahlbeton-Bauten bietet es sich an, die Betonbewehrung zu benutzen: - Sie kann die Funktionen der Ableitungseinrichtungen und des Blitzschutz- Potentialausgleichs bei einem klassischen Gebäude-Blitzschutz übernehmen [1]; - Sie kann, ggf. bei entsprechender Ergänzung, als ein geschlossener Käfig ausgebildet werden und damit eine deutliche Reduzierung der Belastung elektrischer / elektronischer Systeme durch blitzinduzierte elektromagnetische Felder erbringen (LEMP-Schutz [2]). Die Nutzung der Bewehrung ist dabei grundsätzlich gleichermaßen bei Neubauten wie auch bei Ertüchtigungen möglich und sinnvoll. So stellt die Nutzung der Bewehrung beispielsweise im Bereich von Großkraftwerken eine wesentliche Ertüchtigungsmaßnahme für den Blitzschutz elektrischer und elektronischer Einrichtungen dar: - Einerseits wird der Blitzschutz-Potentialausgleich durch den Anschluss metallener Einrichtungen wie Elektronik-Schränke, Kabeltrag-Konstruktionen, Rohrleitungen, etc. an die Bewehrung deutlich verbessert. - Andererseits kann bei größeren Gebäuden die elektromagnetische Schirmwirkung durch die elektrische Überbrückung von vorhandenen Dehnfugen bei Stahlbetonbauten optimiert werden. Diese Dehnfugen sind teilweise nur unzureichend überbrückt, so dass bei Blitzeinschlag in das betreffende oder ein benachbartes Gebäude an Kabelstrecken, die über die Dehnfuge hinwegführen, rel. hohe Spannungen induziert werden können [2, 3]. Die sich um das gesamte Gebäude herumziehende oder zwischen zwei Gebäuden befindliche Dehnfuge muss deshalb im Abstand von maximal einigen Metern überbrückt werden. Im Falle von Blitzschutz-Ertüchtigungen in vorhandenen Gebäuden wird bisher an jeder geplanten Anschlussstelle die Bewehrung großflächig (∅ wenige 10 cm) freigelegt, dort ein elektrischer Anschluss zu dem Bewehrungsstab hergestellt, z.B. mittels eines Erdungsfestpunkts, und dann die Betonoberfläche wieder geschlossen. Je nach prognostizierter Strombelastung wird teilweise versucht, den über den Anschluss fließenden Strom bereits auf mehrere Bewehrungsstäbe zu verteilen. Dazu sind entweder die kreuzenden Stäbe zu verschweißen oder es sind direkt Anschlüsse an zwei Bewehrungsstäbe herzustellen. All dieses bedeutet einen hohen Aufwand bei der Freilegung der Bewehrung und auch wieder bei der Schließung der entstandenen Betonlöcher. Es soll deshalb hier untersucht werden, ob es beispielsweise zum Zwecke des Blitzschutz-Potentialausgleichs und auch zur Überbrückung von Dehnfugen ausreichend ist, den Anschluss an die Bewehrung nach einfachen Verfahren nur jeweils an einen Bewehrungsstab herzustellen. Damit würde der finanzielle und administrative Aufwand an Betonarbeiten deutlich reduziert. Die hier dargestellten Verfahren sind dabei insbesondere für den Einsatz bei Blitzschutz-Ertüchtigungen in bestehenden Gebäuden vorgesehen. Abschließend sollen deshalb die Möglichkeiten zur Prüfung korrekter Anschlüsse, die Grenzen der Verfahren sowie auch die Grenzen der Anwendbarkeit bei Neuanlagen diskutiert werden. KW - Blitzschutz KW - Stahlbetonkonstruktion KW - Lightning Protection KW - reinforced concrete Y1 - 2001 ER - TY - CHAP A1 - Kern, Alexander A1 - Neskakis, Apostolos A1 - Müller, Klaus-Peter T1 - Blitzschutzkonzept für eine netz-autarke Hybridanlage am Beispiel der Anlage VATALI auf Kreta N2 - Netz-autarke Anlagen bestehen üblicherweise aus einer oder mehreren Photovoltaik- (PV-) Anlagen, ggf. auch Solarthermie- (ST-) Anlagen und einem oder mehreren kleineren Windgeneratoren (sie werden deshalb auch als Hybridanlagen bezeichnet) und werden vor allem in Gegenden mit sehr schlechter öffentlicher Energieversorgung eingesetzt, d.h. insbesondere in rel. dünn bewohnten Gebieten und in Entwicklungsländern. Der Blitzschutz von netz-autarken Hybridanlagen ist ein bislang noch vergleichsweise unzureichend bearbeitetes Fachgebiet. Für große Windenergie-Anlagen (WEA) wurde in den letzten Jahren eine Zahl von FuE-Projekten durchgeführt, zum Großteil finanziert durch die öffentliche Hand, zum kleineren Teil auch durch die Industrie, d.h. die WEAHersteller. Dabei wurden bestehende Defizite im Design der WEA festgestellt und Maßnahmen vorgeschlagen, die vor den mechanischen Zerstörungen insbesondere des Rotors und vor den Störungen und Zerstörungen an den elektrischen / elektronischen Systemen der WEA weitgehend Schutz bieten [1, 2, 3]. Der Stand-der- Normung ist im Entwurf DIN VDE 0127 Teil 24 „Blitzschutz für Windenergieanlagen“ (dt. Übersetzung des internationalen Drafts IEC 61400-24 „Wind turbine generator systems; Part 24: Lightning Protection“) dokumentiert [4]. Die Maßnahmen sind allerdings insbesondere für größere WEA vorgesehen; im Falle kleinerer WEA lassen sie sich nur bedingt umsetzen. Trotzdem sind auch kleinere WEA rel. stark blitzeinschlaggefährdet, wenn sie auf einer Bergkuppe o.ä. platziert werden. Für solche kleinere WEA, wie sie bei Hybridanlagen üblicherweise Verwendung finden, müssen die Blitzschutzmaßnahmen aus der DIN VDE 0127 Teil 24 angepasst werden. Für PV- und ST-Anlagen ist eine entsprechende Blitzschutz-Norm noch nicht in Sicht. Hier ist vor allem der Schutz gegen direkte Blitzeinschläge in die Anlage bzw. die Gebäude noch nicht ausreichend beachtet. Blitzfangeinrichtungen sind oft nicht vorgesehen. In aller Regel hat man dabei bisher eine Ausführungsform des Blitzschutzes realisiert, die primär einen Ferneinschlag berücksichtigt und die dabei entstehenden induzierten, rel. energieschwachen Überspannungen durch schwächere Schutzelemente wie Rückstromdioden, Bypassdioden und zum Teil thermisch überwachte Varistoren begrenzt [5, 6, 7]. Diese Schutzelemente können allerdings bei Naheinschlägen bzw. Direkteinschlägen überlastet und damit zerstört werden. Darüber hinaus können Nahoder Direkteinschläge auch zur Schwächung der elektrischen Festigkeit der PVModulisolierung führen. Die Folge davon sind lokale extreme Wärmeentwicklungen, die sogar ein Schmelzen von Glas (sekundärer Langzeiteffekt) hervorrufen könnten. Bei einem Blitzeinschlag in die netz-autarke Hybridanlage VATALI auf Kreta im Jahre 2000 wurden sowohl einige mechanische wie auch elektrische Komponenten der Anlage zerstört bzw. zum Teil schwer beschädigt. Die Anlage VATALI besaß zum Zeitpunkt des Blitzeinschlags keinen wirksamen Blitzschutz. Der Gesamtschaden der Hardware belief sich auf ca. 60.000,- EURO. Die exponierte Stellung der Anlage auf einer Bergspitze stellte und stellt nach wie vor ein enormes Blitzeinschlag-Risiko dar, so dass auch zukünftig mit Blitzeinwirkungen gerechnet werden muss. Die Anlage wurde inspiziert, blitzschutz-technische Erfordernisse definiert und daraus Ertüchtigungsmaßnahmen abgeleitet, die mit überschaubarem Aufwand realisierbar sind. KW - Blitzschutz KW - Hybridanlage KW - Regenerative Energieanlagen KW - Lightning protection KW - renewable energy KW - hybrid system Y1 - 2001 ER - TY - CHAP A1 - Kern, Alexander A1 - Krichel, Frank A1 - Müller, Klaus-Peter T1 - Lightning protection design of a renewable energy hybrid-system without power mains connection N2 - In the year 2000 a direct lightning strike to the hybridsystem without power mains connection VATALI on the Greek island Crete results in the destruction and damage of some mechanical and electrical components. The hybrid-system VATALI was not lightning protected at that time. The hardware damage costs are approx. 60,000 €. The exposed site of the hybrid-system on top of a mountain was and still is the reason for a high risk of lightning strikes. Also in the future further lightning strikes have to be taken into consideration. In the paper a fundamental lightning protection design concept for renewable energy hybrid-systems without power mains connection and protection measures against direct strikes and overvoltages are shown in detail. The design concept was realized exemplarily for the hybrid-system VATALI. The hardware costs for the protection measures were about 15,000 €. About 50% of the costs are due to protection measures against direct strikes, 50% are due to overvoltage protection. Future extensions, new installations, or modifications have to be included into the lightning protection design concept of the hybrid-system. KW - Blitzschutz KW - Erneuerbare Energien KW - Hybridsystem KW - Lightning protection KW - Renewable energy KW - hybrid-system Y1 - 2001 ER - TY - JOUR A1 - Kern, Alexander A1 - Heidler, Fridolin A1 - Zischank, Wolfgang J. A1 - Frentzel, Ralf T1 - Lightning current distribution and coupling to control cables in power plants or large industrial facilites Y1 - 2002 N1 - International Conference on Grounding and Earthing <2002, Rio de Janeiro> ER - TY - JOUR A1 - Kern, Alexander A1 - Landers, E.-U. T1 - Die neuen Blitzschutz-Vornormen der Reihe VDE-V 0185:2002 Y1 - 2002 ER - TY - CHAP A1 - Kern, Alexander T1 - Risikomanagement : Abschätzung des Schadensrisikos für bauliche Anlagen - Die neue Vornorm DIN V VDE V 0185 Teil 2 : 2002 N2 - Alle Unternehmen sind vielfältigen Risiken ausgesetzt, die Finanz- und Betriebsbereiche einschließlich Dienstleistungen betreffen können. Die Firmen müssen üblicherweise Risiken eingehen, um im Wettbewerb bestehen zu können. Entscheidend ist, dass man sich über die Risiken bewusst ist, diese einschätzen und kontrollieren kann. Falsche Einschätzungen, Versäumnisse und Fehlentscheidungen können empfindliche finanzielle Schäden bis hin zum Totalverlust nach sich ziehen. Ein effektives Risikomanagement ist heute als wichtiger Sicherheitsfaktor anzusehen und sollte zur strategischen Unternehmensführung gehören. Ein vorausschauendes Risikomanagement beinhaltet, Risiken für das Unternehmen zu kalkulieren. Es liefert Entscheidungsgrundlagen, um diese Risiken zu begrenzen und es macht transparent, welche Risiken sinnvollerweise über Versicherungen abgedeckt werden sollten. Beim Versicherungsmanagement ist jedoch zu bedenken, dass zur Erreichung bestimmter Ziele Versicherungen nicht geeignet sind (z.B. Erhaltung der Lieferfähigkeit). Eintrittswahrscheinlichkeiten bestimmter Risiken lassen sich durch Versicherungen nicht verändern. Bei Unternehmen, die mit umfangreichen elektronischen Einrichtungen produzieren oder Dienstleistungen erbringen (und das sind heutzutage wohl die meisten), muss auch das Risiko durch Blitzeinwirkungen besondere Berücksichtigung finden. Dabei ist zu beachten, dass der Schaden aufgrund der Nicht-Verfügbarkeit der elektronischen Einrichtungen und damit der Produktion bzw. der Dienstleistung und ggf. der Verlust von Daten den Hardware-Schaden an der betroffenen Anlage oft bei weitem übersteigt. Im Blitzschutz gewinnt innovatives Denken in Schadensrisiken langsam an Bedeutung. Risikoanalysen haben die Objektivierung und Quantifizierung der Gefährdung von baulichen Anlagen und ihrer Inhalte durch direkte und indirekte Blitzeinschläge zum Ziel. Seinen Niederschlag hat dieses neue Denken in der neuen deutschen Norm DIN V 0185-2 VDE V 0185 Teil 2 gefunden. Die hier vorgegebene Risikoanalyse gewährleistet, dass ein für alle Beteiligten nachvollziehbares Blitzschutz-Konzept erstellt werden kann, das technisch und wirtschaftlich optimiert ist, d.h. bei möglichst geringem Aufwand den notwendigen Schutz gewährleisten kann. Die sich aus der Risikoanalyse ergebenden Schutzmaßnahmen sind dann in den weiteren Normenteilen der neuen Reihe VDE V 0185 detailliert beschrieben. KW - Blitzschutz KW - Risikomanagement KW - Risikoabschätzung KW - Versicherung KW - Lightning protection KW - Risk management KW - Risk assessment ; Insurance Y1 - 2002 ER - TY - CHAP A1 - Darveniza, M. A1 - Flisowski, Z. A1 - Kern, Alexander A1 - Landers, E.-U. A1 - LoPiparo, G. A1 - Mazzetti, C. A1 - Rousseau, A. A1 - Sherlock, J. T1 - Application problems of the probabilistic approach to the assessment of risk for structures and services N2 - The paper deals with the development of the probabilistic approach to the assessment of risk due to lightning. Sources of damage, types of damage and types of loss are defined and, accordingly, the procedure for risk analysis and the way of assessment of different risk components is proposed. The way to evaluate the influence of different protection measures (lightning protection system; shielding of structure, cables and equipment; routing of internal wiring; surge protective device) in reducing such probabilities is considered. The paper has been prepared within the framework of the activity of IEC TC81-WG9/CLC TC81-WG4 directed to prepare the draft IEC 62305-2 Risk Management, in cooperation with the Secretary of IEC/CLC TC81. KW - Blitzschutz KW - Risikoabwägung KW - Lightning protection system KW - risk assessment KW - protection measures Y1 - 2002 ER - TY - CHAP A1 - Kern, Alexander A1 - Krichel, Frank T1 - Considerations about the lightning protection system of mains independent renewable energy hybrid-systems - practical experiences N2 - In the paper a lightning protection design concept for renewable energy hybrid-systems without power mains connection is described. Based on a risk analysis protection measures against direct strikes and overvoltages are shown in an overview. The design concept is realized exemplarily for the hybrid-system VATALI on the Greek island Crete. VATALI, not lightning protected at that time, was a victim of a lightning strike in the year 2000 causing destructions and damages of some mechanical and electrical components with costs of approx. 60.000 €. The hardware costs for the protection measures were about 15.000 €: about 50% of the costs are due to protection measures against direct strikes, 50% are due to overvoltage protection. KW - Blitzschutz KW - Erneuerbare Energien KW - Hybridsystem KW - Photovoltaikanlage KW - Windenergieanlage KW - Lightning protection KW - renewable energy KW - hybrid system KW - photovoltaic system KW - wind turbine Y1 - 2002 ER - TY - CHAP A1 - Zischank, Wolfgang J. A1 - Heidler, Fridolin A1 - Kern, Alexander A1 - Metwally, I. A. A1 - Wiesinger, J. A1 - Seevers, M. T1 - Laboratory simulation of direct lightning strokes to a modelled building - measurement of magnetic fields and induced voltages N2 - In IEC 61312-2 equations for the assessment of the magnetic fields inside structures due to a direct lightning strike are given. These equations are based on computer simulations for shields consisting of a single-layer steel grid of a given mesh width. Real constructions, however, contain at least two layers of reinforcement steel grids. The objective of this study was to experimentally determine the additional shielding effectiveness of a second reinforcement layer compared to a single-layer grid. To this end, simulated structures were set up in the high current laboratory. The structures consisted of cubic cages of 2 m side length with one or with two reinforcement grids, respectively. The structures were exposed to direct lightning currents representing the variety of anticipated lightning current waveforms. The magnetic fields and their derivatives at several positions inside the structure as well as the voltage between “floor” and “roof” in the center were determined for different current injection points. From these data the improvement of the shielding caused by a second reinforcement layer is derived. KW - Direkter Blitzschlag KW - Elektromagnetischer Schutzschild KW - Magnetische Felder KW - Induzierte Spannungen KW - Stahlbetonkonstruktion KW - Lightning KW - electromagnetic shielding KW - magnetic field KW - reinforced concrete KW - induced voltage Y1 - 2002 ER - TY - CHAP A1 - Kern, Alexander T1 - Abschätzung des Blitzschadensrisikos für bauliche Anlagen - Die neue Bestimmung DIN V VDE V 0185 Teil 2 : 2002 - Allgemeines, Abschätzungsverfahren, Berechnungsbeispiele N2 - Ein vorausschauendes Risikomanagement beinhaltet, Risiken für das Unternehmen zu kalkulieren. Es liefert Entscheidungsgrundlagen, um diese Risiken zu begrenzen und es macht transparent, welche Risiken sinnvollerweise über Versicherungen abgedeckt werden sollten. Beim Versicherungsmanagement ist jedoch zu bedenken, dass zur Erreichung bestimmter Ziele Versicherungen nicht immer geeignet sind (z.B. Erhaltung der Lieferfähigkeit). Eintrittswahrscheinlichkeiten bestimmter Risiken lassen sich durch Versicherungen nicht verändern. Bei Unternehmen, die mit umfangreichen elektronischen Einrichtungen produzieren oder Dienstleistungen erbringen (und das sind heutzutage wohl die meisten), muss auch das Risiko durch Blitzeinwirkungen besondere Berücksichtigung finden. Dabei ist zu beachten, dass der Schaden aufgrund der Nicht-Verfügbarkeit der elektronischen Einrichtungen und damit der Produktion bzw. der Dienstleistung und ggf. der Verlust von Daten den Hardware-Schaden an der betroffenen Anlage oft bei weitem übersteigt. Im Blitzschutz gewinnt innovatives Denken in Schadensrisiken langsam an Bedeutung. Risikoanalysen haben die Objektivierung und Quantifizierung der Gefährdung von baulichen Anlagen und ihrer Inhalte durch direkte und indirekte Blitzeinschläge zum Ziel. Seinen Niederschlag hat dieses neue Denken in der neuen deutschen Vornorm DIN V 0185-2 VDE V 0185 Teil 2 [1] gefunden. Die hier vorgegebene Risikoanalyse gewährleistet, dass ein für alle Beteiligten nachvollziehbares Blitzschutz-Konzept erstellt werden kann, das technisch und wirtschaftlich optimiert ist, d.h. bei möglichst geringem Aufwand den notwendigen Schutz gewährleisten kann. Die sich aus der Risikoanalyse ergebenden Schutzmaßnahmen sind dann in den weiteren Normenteilen der neuen Reihe VDE V 0185 [2, 3] detailliert beschrieben. KW - Blitzschutz KW - Risikomanagement KW - Risikoabschätzung KW - Lightning protection KW - Risk management KW - Risk assessment Y1 - 2003 ER - TY - JOUR A1 - Kern, Alexander T1 - Risikomanagement für den Blitzschutz - Abschätzung des Blitzschadensrisikos nach der neuen Vornorm VDE V 0185 Teil 2 : 2002 N2 - Ein vorausschauendes Risikomanagement beinhaltet, Risiken zu kalkulieren. Es liefert Entscheidungsgrundlagen, um diese Risiken zu begrenzen und es macht transparent,welche Risiken sinnvoll über Versicherungen abgedeckt werden sollten. Bei Unternehmen, die mit umfangreichen elektronischenEinrichtungen produzieren oder Dienstleistungen erbringen (und das sind heutzutage wohl die meisten), muss auch das Risiko durch Blitzeinwirkungen besondere Berücksichtigung finden. Dabei ist zu beachten, dass der Schaden aufgrund der Nichtverfügbarkeit der elektronischen Einrichtungen und damit derProduktion bzw. der Dienstleistung und ggf. der Verlust von Daten den Hardwareschaden an der betroffenen Anlage oft bei weitem übersteigt. KW - Blitzschutz KW - Risikomanagement KW - Risikoabschätzung KW - Lightning protection KW - Risk management KW - Risk assessment Y1 - 2003 ER - TY - CHAP A1 - Krichel, Frank A1 - Kern, Alexander A1 - Krämer, Heinz-Josef A1 - Wettingfeld, Jürgen A1 - Reetz, Josef A1 - Kienlein, Manfred T1 - Blitzschutzmaßnahmen für Photovoltaik- und kleine Windenergieanlagen – Einige Beispiele T1 - Lightning Protection for photovoltaic and small wind energy power plants N2 - Ein von der Arbeitsgemeinschaft (AG) Solar NRW und diversen Industriepartnern gefördertes und an der Fachhochschule Aachen, Abt. Jülich durchgeführtes Forschungsprojekt „Blitzschutz für netz-autarke Hybridanlagen“ machte es möglich, sich mit dem Blitzschutz speziell solcher Anlagen näher zu beschäftigen. Vermehrt bekannt gewordene Schadensfälle an nicht netz-gekoppelten Hybridanlagen waren der Auslöser, den Schutz zu überdenken. Definiertes Ziel war es, für netz-autarke energietechnische Anlagen ein Konzept zum Schutz vor Blitzeinwirkungen zu erstellen. Diese Anlagen bestehen üblicherweise aus einer oder mehreren Photovoltaikanlagen, ggf. auch Solarthermieanlagen und einem oder mehreren kleineren Windgeneratoren (sie werden deshalb auch als Hybridanlagen bezeichnet). Zur Erhöhung der Versorgungssicherheit kann noch ein Dieselaggregat dazukommen. Hybridanlagen werden vor allem in Gebieten mit sehr schlechter öffentlicher Energieversorgung eingesetzt, d.h. insbesondere in relativ dünn bewohnten Gebieten und in Entwicklungsländern. Dem Blitzschutz von Hybridanlagen kommt dabei eine steigende Bedeutung zu. Besonderes Augenmerk in dem genannten Forschungsprojekt sollte dabei auf die technisch/wirtschaftliche Ausgewogenheit des Schutzes gelegt werden: • die Schutzmaßnahmen sollen nur in solchen Fällen eingesetzt werden, wo dies als Ergebnis von Risikoanalysen sinnvoll erscheint; • für typische netz-autarke Hybridanlagen sollen die Schutzmaßnahmen ohne deutliche Verteuerung realisierbar sein (es soll also kein absoluter Schutz realisiert werden; ggf. soll lediglich der auftretende Schaden soweit möglich minimiert werden). Dazu wurde in einem ersten Schritt zunächst eine Aufnahme des Iststandes einiger typischer netz-autarker Hybridanlagen und deren einzelnen Komponenten durchgeführt. Aufgrund dessen wurde eine umfassende Risikoanalyse zur Blitzbedrohung dieser Anlagen auf der Basis von VDE V 0185 Teil 2:2002-11 [1] erstellt. Die Ergebnisse mündeten in ein technisch/wirtschaftlich ausgewogenes Konzept für den Anlagen- Blitzschutz (d.h. insbesondere dem Schutz vor direkten Blitzeinschlägen und deren unmittelbaren Auswirkungen) nach VDE V 0185 Teil 3:2002-11 [2] und für den Elektronik-Blitzschutz (d.h. für den Schutz vor Überspannungen durch direkte, insbesondere aber auch indirekte Blitzeinschläge) nach VDE V 0185 Teil 4:2002-11 [3]. Aufgrund der gesammelten Ergebnisse konnten dabei allgemeine Empfehlungen für den Äußeren und Inneren Blitzschutz von regenerativen Energieerzeugungssystemen erstellt werden. Diese sollen in Schulungen einmünden, die für Hersteller und Betreiber von Hybridanlagen angeboten werden. Durch die Anwendung wird der Schutz der Anlagen vor Blitzeinwirkung und elektromagnetischen Störungen verbessert, was sich in einer reduzierten Ausfallwahrscheinlichkeit bzw. erhöhten Verfügbarkeit wiederspiegelt. An einigen ausgewählten Anlagen werden mit Hilfe der im Projekt involvierten Industriepartner die Schutzmaßnahmen realisiert. Hierbei entstanden den Eigentümern bzw. Betreibern der Anlagen keine Kosten. In diesem Beitrag werden beispielhaft drei Anlagenprojekte detailliert gezeigt. Es handelt sich dabei um eine Schweinezuchtfarm in Magallón (Spanien, Zaragozza), das bioklimatische Haus (Kreta, Heraklion) und die Tegernseer- Hütte (Deutschland, Lenggries). KW - Blitzschutz KW - Photovoltaikanlagen KW - Windenergieanlagen KW - Lightning protection KW - photovoltaic system KW - wind turbine Y1 - 2003 ER - TY - CHAP A1 - Kern, Alexander T1 - Risikomanagement nach DIN V 0185-2 VDE V 0185 Teil 2: 2002-11 - Einige Beispiele und erste Erfahrungen T1 - Risk management based on DIN V 0185-2 VDE V 0185 part 2: 2002-11 - Some examples and first experiences N2 - Die neue Vornorm VDE V 0185 Teil 2 „Risikomanagement: Abschätzung des Schadensrisikos für bauliche Anlagen“ [1] ist seit November 2002 gültig. Sie ermöglicht nicht nur die Ermittlung der Schutzklasse eines Blitzschutzsystems, sondern auch die Untersuchung zur Notwendigkeit anderer Schutzmaßnahmen gegen Blitzeinwirkungen (Überspannungsschutzgeräte in Unterverteilern und/oder an Endgeräten, Schirmung des Gebäudes und/oder interner Räume, Potentialsteuerung, Brandmelde- und Feuerlöscheinrichtungen, etc.) nach objektiven Kriterien und damit in einer für alle Beteiligten grundsätzlich nachvollziehbaren Art und Weise. Dass eine solche Analyse rel. komplex sein muss und der intensiven Beschäftigung bedarf, ist deshalb nicht verwunderlich. Die Komplexität des Verfahrens sollte allerdings nicht dazu führen, die Vornorm als Ganzes abzulehnen. Die Vornorm beruht auf dem Stand der Diskussion im internationalen Normengremium IEC TC81 WG9 Ende des Jahres 2000. Integriert wurden einige nationale Besonderheiten, die aus Sicht des zuständigen Normenkomitees DKE K251 erforderlich erschienen. In Deutschland konnten und können nun erste breite Erfahrungen in der Anwendung dieser Risikoanalyse gesammelt werden; in anderen Ländern ist dies noch nicht möglich. Diese Erfahrungen können dann, nach Diskussion im nationalen Rahmen, in die internationale Normenarbeit eingebracht werden. Im folgenden Beitrag sollen einige, seit Erscheinen der Vornorm oft wiederkehrende Fragen dargestellt und Lösungsvorschläge vorgestellt werden. Dabei wird auch auf die Tendenzen im internationalen Normengremium IEC TC81 WG9 eingegangen, d.h. auf den aktuellen Entwurf zur IEC 62305-2 [3]. Die Lösungsvorschläge werden begründet, sind allerdings weitestgehend subjektive Meinung des Autors. Für übliche bauliche Anlagen ist die Anwendung der Vornorm rel. einfach möglich. Auch für spezielle Fälle können die darin festgelegten Verfahren herangezogen werden; allerdings sind dann einige weiterführende Überlegungen notwendig, die der Planer von Blitzschutzsystemen durchführen muss. Anhand zweier Beispiele soll die Anwendung der VDE V 0185 Teil 2 auf solche speziellen Fälle dargestellt werden. KW - Blitzschutz KW - Risikomanagement KW - Lightning protection KW - risk management Y1 - 2003 ER - TY - CHAP A1 - Kern, Alexander A1 - Krämer, Heinz-Josef T1 - Blitzschutzkonzept für eine bauliche Anlage mit Stahlkonstruktion und metallenen Wänden N2 - Bauliche Anlagen mit Stahlkonstruktionen (bzw. auch Stahlbetonskelett- Konstruktionen) und metallenen Wänden sind bereits in sehr großer Zahl errichtet. Dazu gehören kleinere bis größere Lagerhallen ebenso wie Einkaufszentren. Sie zeichnen sich durch große Flexibilität, einfache Planung, kurze Bauzeit und rel. geringe Kosten aus. Auch in der nahen Zukunft ist deshalb mit Planung und Errichtung weiterer solcher baulicher Anlagen zu rechnen. Abhängig von der Nutzung der Hallen sind auch mehr oder weniger umfangreiche elektrische und elektronische Systeme vorhanden, die wichtige Funktionen sicherstellen müssen. Der Blitzschutz für diese baulichen Anlagen sollte sich also nicht nur im „klassischen“ Gebäude-Blitzschutz nach DIN V 0185-3 VDE V 0185 Teil 3 [1] erschöpfen; ein Ergänzung hin zu einem sinnvollen Grundschutz der elektrischen und elektronischen Systeme nach DIN V 0185-4 VDE V 0185 Teil 4 [2] ist anzuraten. Im folgenden Beitrag wird ein Konzept vorgestellt, mit dem ein hochwertiger Blitzschutz sowohl der baulichen Anlage und der darin befindlichen Personen, als auch der elektrischen und elektronischen Systeme verwirklicht werden kann. Insbesondere bei großflächigen Hallen stellen sich dabei besondere Anforderungen. Das Konzept und die zugehörigen blitzschutz-technischen Maßnahmen können drei Hauptbereichen zugeordnet werden: - Äußerer Blitzschutz; - Innerer Blitzschutz; - weitergehende besondere Maßnahmen. Das Konzept sowie die Maßnahmen werden allgemein beschrieben und teilweise anhand einer ausgeführten Anlage mit Fotos beispielhaft dokumentiert. KW - Blitzschutz KW - Stahlbetonkonstruktion KW - Lightning protection KW - reinforced concrete Y1 - 2003 ER - TY - JOUR A1 - Kern, Alexander A1 - Krichel, Frank T1 - Überlegungen zum Blitzschutzkonzept für regenerative Energieanlagen N2 - Dem Blitzschutz von Anlagen der regenerativen Energien kommt in Zukunft eine steigende Bedeutung zu. Dabei ist es notwendig zu berücksichtigen, dass die Schutzmaßnahmen technisch/wirtschaftlich ausgewogen sind. Erbauer, Besitzer oder Benutzer von netzautarken Hybridanlagen haben zu entscheiden, ob die Anlage einen Schutz braucht oder nicht. Um diese Entscheidung zu fällen, ist eine Risikoanalyse als erster Schritt sinnvoll. Diese muss dabei die für die Hybridanlage relevanten Schadenarten und spezifischen Parameter, Werte und Randbedingungen mit einbeziehen. Dazu ist die Hilfe eines Blitzschutzexperten sehr hilfreich. KW - Alternative Energiequelle KW - Energietechnische Anlage KW - Blitzschutz KW - Blitzschutz KW - Regenerative Energieanlagen KW - Lightning protection KW - renewable energy Y1 - 2003 ER - TY - JOUR A1 - Kern, Alexander A1 - Krichel, Frank T1 - Considerations about the lightning protection system of mains independent renewable energy hybrid-systems - practical experiences JF - Journal of electrostatics. 60 (2004), H. 2-4 Y1 - 2004 SN - 0304-3886 N1 - ISSN der E-Ausg.: 0304-3886 SP - 257 EP - 263 ER - TY - BOOK A1 - Kern, Alexander T1 - Blitz- und Überspannungsschutz für Anlagen der regenerativen Energietechnik Y1 - 2004 PB - Fachhochschule Aachen, Abt. Jülich CY - Aachen ER - TY - JOUR A1 - Zischank, Wolfgang J. A1 - Heidler, Fridolin A1 - Wiesinger, J. A1 - Metwally, I. A1 - Kern, Alexander A1 - Seevers, M. T1 - Laboratory simulation of direct lightning strokes to a modeled building : measurement of magnetic fields and included voltages JF - Journal of electrostatics. 60 (2004), H. 2 - 4 Y1 - 2004 SN - 0304-3886 N1 - ISSN der E-Ausg.: 0304-3886 SP - 223 EP - 232 ER - TY - CHAP A1 - Surtees, A. J. A1 - Gillespie, A. A1 - Kern, Alexander A1 - Rousseau, A. T1 - DEVELOPMENT OF A RISK ASSESSMENT CALCULATOR BASED ON A SIMPLIFIED FORM OF THE IEC 62305-2 STANDARD ON LIGHTNING PROTECTION N2 - Neue Blitzschutznorm IEC 62305. Entwicklung einer einfachen Software zur Risikoabwägung N2 - IEC Technical Committee 81 is currently creating the new IEC 62305 series of standards on Lightning Protection. Working Group 9 is responsible for Part 2 of this series, which deals with the assessment and management of risk its CDV (Committee Draft for Voting) stage and has been circulated to National Committees for comment. The paper details the development of the Simplified IEC Risk Assessment Calculator software tool as described in Informative Annex J of IEC62305-2 Ed.1/CDV 2. This tool is intended as a simplified implementation of the more rigorous treatment of risk management found in the written document. It is designed to be relatively intuitive for users who wish to obtain an initial assessment of risk sensitivity, but should not be considered a substitute to a full understanding of the methods provided in the standard when dealing with more complicated structures or those where greater risks to personal or system operation are involved. KW - Risiko KW - Risikoabwägung KW - Blitzrisiko KW - Blitzschutz KW - Risk KW - Risk Management KW - Risk Assessment KW - Lightning Risk KW - Lightning Protection Y1 - 2004 ER - TY - CHAP A1 - Kern, Alexander A1 - Heidler, Fridolin A1 - Seevers, M. A1 - Zischank, Wolfgang J. T1 - Magnetic Fields and Induced Voltages in case of a Direct Strike - Comparison of Results obtained from Measurements at a Scaled Building to those of IEC 62305-4 N2 - In the paper the results obtained from experiments at a modelled reinforced building in case of a direct lightning strike are compared with calculations. The comparison includes peak values of the magnetic field Hmax, its derivative (dH/dt)max and of induced voltages umax in typical cable routings. The experiments are performed at a 1:6 scaled building and the results are extrapolated using the similarity relations theory. The calculations are based on the approximate formulae given in IEC 62305-4 and have to be supplemented by a rough estimation of the additional shielding effect of a second reinforcement layer. The comparison shows, that the measured peak values of the magnetic field and its derivative are mostly lower than the calculated. The induced voltages are in good agreement. Hence, calculations of the induced voltages based on IEC 62305-4 are a good method for lightning protection studies of buildings, where the reinforcement is used as a grid-like electromagnetic shield. N2 - Auswirkungen eines direkten Blitzeinschlages auf ein Gebäude, Vergleich von experimentellen Ergebnissen und Berechnungen basierend auf einer Formel aus der IEC 62305-4 KW - Blitz KW - Direkter Blitzschlag KW - Elektromagnetischer Schutzschild KW - Magnetische Felder KW - Induzierte Spannungen KW - Kalkulation KW - Direct lightning strike KW - electromagnetic shield KW - magnetic fields KW - induced voltages KW - calculations Y1 - 2004 SN - 0304-3886 N1 - Journal of electrostatics: Beitr. auf S. 379 - 385. doi:10.1016/j.elstat.2006.09.004 ER - TY - CHAP A1 - Zischank, Wolfgang J. A1 - Heidler, Fridolin A1 - Wiesinger, J. A1 - Stimper, K. A1 - Kern, Alexander A1 - Seevers, M. T1 - Magnetic Fields and Induced Voltages inside LPZ 1 Measured at a 1:6 Scale Model Building N2 - Laborexperimente zu Blitzschutzzonen in Stahlbetongebäuden anhand eines Modells im Maßstab 1:6 N2 - For the application of the concept of Lightning Protection Zones (LPZ), the knowledge of the magnetic fields and induced voltages inside a structure is necessary. Laboratory experiments have been conducted at a downscaled model of a building (scale factor 1:6) to determine these electromagnetic quantities in case of a direct strike to the structure. The model (3 m x 2 m x 2 m) represented a small industrial building using the reinforcement of the concrete as electromagnetic shield. The magnetic fields and magnetic field derivatives were measured at several location inside the scaled model. Further, the voltages induced on three typical cable routes inside the model was determined. The influence of the lightning current waveshape, point-of-strike, bonding of the cable routes, and bridging of an expansion joint in the middle of the building on these quantities was studied. KW - Blitzschlag KW - Elektromagnetischer Schutzschild KW - Stahlbeton KW - Maßstabsgetreues Modell KW - Lightning KW - electromagnetic shielding KW - reinforced concrete KW - scaled model Y1 - 2004 ER - TY - JOUR A1 - Kern, Alexander A1 - Landers, E.-U. A1 - Scheibe, K. A1 - Zahlmann, P. T1 - Die künftige deutsche Blitzschutznormung (1) : Reihe DIN EN 62305 / VDE 0185-305-x:2006 JF - De : der Elektro- und Gebäudetechniker / Ausgabe ZV. 81 (2006), H. 15-16 Y1 - 2006 SN - 1617-1160 N1 - In der Bibliothek vorhanden: 23 Z 863 (Bibliothek Eupener Str.) SP - 26 EP - 30 ER - TY - JOUR A1 - Kern, Alexander T1 - Die neuen Blitzschutznormen der Reihe DIN EN 62305 (VDE 0185-305-x) JF - ETZ : Elektrotechnik + Automation. 2006 (2006), H. 2 Y1 - 2006 SN - 0170-1711 N1 - 2. ISSN: 0948-7387 ; In der Bibliothek unter 23 Z 133 (Eupener Str.) und 63 ZS 035 (Jülich) vorhanden. SP - 42 EP - 45 ER - TY - JOUR A1 - Kern, Alexander A1 - Landers, E.-U. T1 - Die künftige deutsche Blitzschutznormung (2/3) – Reihe DIN EN 62305:2006 – Teil 2: Risikomanagement JF - De : der Elektro- und Gebäudetechniker / Ausgabe ZV. 81 (2006), H. 18 - 19 Y1 - 2006 SN - 1617-1160 ER - TY - JOUR A1 - Kern, Alexander T1 - Neue deutsche Blitzschutz-Normung. Reihe DIN EN 62305 / VDE 01 85-305-x:2006 JF - Der Eisenbahningenieur. 58 (2007), H. 8 Y1 - 2007 SN - 0013-2810 N1 - in der Bereichsbibliothek Bayernallee vorhanden SP - 18 EP - 22 ER -