TY - CHAP A1 - Kern, Alexander A1 - Dikta, Gerhard T1 - Probability of damage of electrical and electronic systems due to indirect lightning flashes - investigation of data from German insurance companies N2 - In the presented paper data collected from the field related to damage statistics of electrical and electronic apparatus in household are reported and investigated. These damages (total number approx. 74000 cases), registered by five German insurance companies in 2005 and 2006, were adviced by customers as caused by lightning overvoltages. With the use of stochastical methods it is possible, to reasses the collected data and to distinguish between cases, which are with high probability caused by lightning overvoltages, and those, which are not. If there was an indication for a direct strike, this case was excluded, so the focus was only on indirect lightning flashes, i.e. only flashes to ground near the structure and flashes to or nearby an incoming service line were investigated. The data from the field contain the location of damaged apparatus (residence of the policy holder) and the distances of the nearest cloud-to-ground stroke to the location of the damage registered by the German lightning location network BLIDS at the date of damage. The statistical data along with some complementary numerical simulations allow to verify the correspondence of the Standards rules used for IEC 62305-2 with the field data and to define some correction needs. The results could lead to a better understanding whether a damage reported to an insurance company is really caused by indirect lightning, or not. KW - Blitzschutz KW - lightning flash Y1 - 2009 ER - TY - CHAP A1 - Kern, Alexander A1 - Beierl, Ottmar A1 - Zischank, Wolfgang T1 - Calculation of the separation distance according to IEC 62305-3: 2006-10 - Remarks for the application and simplified methods N2 - [Paper of the X International Symposium on Lightning Protection 9th - 13th November, 2009 - Curitiba, Brazil. 6 pages] The international standard IEC 62305-3, published in 2006, requires as an integral part of the lightning protection system (LPS) the consideration of a separation distance between the conductors of the LPS and metal and electrical installations inside the structure to be protected. IEC 62305-3 gives two different methods for this calculation: a standard, simplified approach and a more detailed approach, which differ especially regarding the treatment of the current sharing effect on the LPS conductors. Hence, different results for the separation distance are possible, leading to some discrepancies in the use of the standard. The standard approach defined in the main part (Clause 6.3) and in Annex C of the standard in some cases may lead to a severe oversizing of the required separation distance. The detailed approach described in Annex E naturally gives more correct results. However, a calculation of the current sharing amongst all parts of the air-termination and downconductor network is necessary, in many cases requiring the use of network analysis programs. In this paper simplified methods for the assessment of the current sharing are presented, which are easy to use as well as sufficiently adequate. KW - Blitzschutz KW - Lightning protection Y1 - 2009 N1 - Paper in: [10. International Symposium on Lightning Protection 9. 13. November 2009, Curitiba, Brasilien. 6 Seiten] ER - TY - CHAP A1 - Behrens, Jörg A1 - Frentzel, Ralf A1 - Kern, Alexander T1 - Simulation der transienten Spannungsverläufe im Eigenbedarfsnetz eines Großkraftwerks bei einem kraftwerksnahen Blitzeinschlag in die Hochspannungs-Freileitung T1 - Simulation of transient voltage curve of a house-load operation net-work of large power plant by a lightning strike in a high-voltage over-head line closed to the power plant N2 - 8. VDE/ABB-Blitzschutztagung, 29. - 30. Oktober 2009 in Neu-Ulm. Blitzschutztagung <8, 2009, Neu-Ulm> Berlin : VDE Verl. 2009 Großkraftwerke können durch Blitzentladungen mit potentiellen Auswirkungen auf deren Verfügbarkeit und Sicherheit gefährdet werden. Ein sehr spezielles Szenario, welches aus aktuellem Anlass zu untersuchen war, betrifft den kraftwerksnahen Blitzeinschlag in die Hochspannungs-Freileitung am Netzanschluss der Anlage. Wird nun noch ein sogenannter Schirmfehler unterstellt, d.h. der direkte Blitzeinschlag erfolgt in ein Leiterseil des Hoch- bzw. Höchstspannungsnetzes und nicht in das darüber gespannte Erdseil, so bedeutet dies eine extreme elektromagnetische Einwirkung. Der vorliegende Beitrag befasst sich mit der Simulation eines solchen Blitzeinschlages und dessen Auswirkungen auf den Netzanschluss und die Komponenten der elektrischen Eigenbedarfsanlagen eines Kraftwerks auf den unterlagerten Spannungsebenen. Die dabei gewonnenen Erkenntnisse lassen sich ohne Einschränkungen auf Industrieanlagen mit Mittelspannungs-Netzanschluss und ohne eigener Stromversorgung übertragen. N2 - Lightning discharge can endanger large power plants with potential influence on their availability and reliability. A very special scenario, which was currently to analyse, is the lightning strike close to the high-voltage overhead line at the grid of the power plant. Supposing a failure of shielding and that the lightning strike goes directly into the line then the elec-tromagnetic effect is extremely high. The following article gives attention to the simulation of lightning strike and their effects to the connection with the grid and the components of the house-load operation of a large power plant especially to the lower voltage level sections. These results are transferable to industrial plants which have no own power supply. KW - Blitzschutz KW - Blitzeinschlag KW - lightning strike Y1 - 2009 SN - 978-3-8007-3197-8 ER - TY - CHAP A1 - Hardt, Arno A1 - Abdel-Gawad, A A1 - Martin, S. A1 - Reich, J. T1 - Design procedures for the Juelich QQDDQ high resolution spectrometer T2 - Proceedings, 5th International Conference on Magnet Technology (MT-5) : Rome, Italy, April 21-25, 1975 Y1 - 1975 SP - 45 EP - 51 ER - TY - CHAP A1 - Dören, Horst-Peter A1 - Molitor, M. A1 - Ertl, Karl-Heinz ED - Lugscheider, Erich T1 - Problematik der Härtemessung an pulverflammgespritzten Verschleißschutzschichten mit Hilfe mobiler, dynamischer Härteprüfverfahren T2 - Thermische Spritzkonferenz : TS 96 ; Vorträge und Posterbeiträge. Essen 6. bis 8. März 1996. DVS-Berichte. Bd. 175 Y1 - 1996 SN - 3-87155-480-4 SP - 249 EP - 254 PB - DVS-Verl. CY - Düsseldorf ER - TY - CHAP A1 - Dören, Horst-Peter A1 - Kröschel, R. ED - Dilthey, Ulrich T1 - Plasma-Spritzen T2 - Schweisszusatzwerkstoffe : Fortschritte, Erfahrungen, Tendenzen. 2. Aachener Schweisstechnik-Kolloquium, 7. bis 8. März 1991 Y1 - 1991 SN - 3-18-140802-6 SP - 147 EP - 167 PB - VDI-Verl. CY - Düsseldorf ER - TY - CHAP A1 - Martin, S. A1 - Berg, G. A1 - Hardt, Arno A1 - Hürlimann, W. A1 - Köhler, M. A1 - Meißberger, J. A1 - Sagefka, T. A1 - Schult, O. W. B. ED - Sanderson, N. E. T1 - First experience with the magnet spectrometer 'BIG KARL' T2 - Use of magnetic spectrometers in nuclear physics : proceedings of the Daresbury study weekend 10 - 11 March 1979 Y1 - 1979 SP - 38 EP - 42 PB - Daresbury Lab. CY - Daresbury ER - TY - CHAP A1 - Dören, Horst-Peter A1 - Wernicke, K. T1 - Auftragen von verschleißfesten stranggegossenen Hartlegierungen auf Kobaltbasis durch das WIG- und Gasschweißen T2 - Schweißen und Schneiden '83 = Welding and Cutting '83. Vorträge der Großen Schweißtechnischen Tagung in Aachen vom 28. bis 30. September 1983. Veranst.: Deutscher Verband für Schweißtechnik (DVS). DVS-Berichte. 83 Y1 - 1983 SN - 3-87155-388-3 SP - 109 EP - 113 PB - Dt. Verl. für Schweißtechnik CY - Düsseldorf ER - TY - CHAP A1 - Dören, Horst-Peter A1 - Lohrmann, G. R. A1 - Wernicke, K. T1 - Plasma-Auftragschweißen mit Metallpulvern und Einsatzmöglichkeiten in der Kerntechnik T2 - Schweissen in der Kerntechnik : Vorträge : internationales Kolloquium. 5 = Welding in nuclear engineering: international conference. 5 = Le soudage dans la technique nucleaire: colloque international. 5 : Nürnberg, 26.11.86-28.11.86. DVS-Berichte. Bd. 106 Y1 - 1986 SN - 3-87155-411-1 SP - 129 EP - 133 PB - Dt. Verl. für Schweißtechnik CY - Düsseldorf ER - TY - CHAP A1 - Dören, Horst-Peter T1 - The examination of surfaces of cold rolled wire for gas-shielded arc-welding T2 - WAI/BISPA joint conference : proceedings. Joint conference of Wire Association International and the British Independent Steel Producers Association (WAI/BISPA) : 26 - 27. 09. 1988, Stratford-upon-Avon Y1 - 1988 SP - 102 EP - 112 CY - Guilford, Conn. ER -