TY - JOUR A1 - Kern, Alexander A1 - Krichel, Frank A1 - Neskakis, Apostolos A1 - Müller, Klaus-Peter (u.a.) T1 - Lightning protection design of a renewable energy hybrid-system without power mains connection Y1 - 2001 N1 - International Conference on Renewable Energies for Islands <2001, Crete> ER - TY - CHAP A1 - Kern, Alexander A1 - Krichel, Frank A1 - Müller, Klaus-Peter T1 - Lightning protection design of a renewable energy hybrid-system without power mains connection N2 - In the year 2000 a direct lightning strike to the hybridsystem without power mains connection VATALI on the Greek island Crete results in the destruction and damage of some mechanical and electrical components. The hybrid-system VATALI was not lightning protected at that time. The hardware damage costs are approx. 60,000 €. The exposed site of the hybrid-system on top of a mountain was and still is the reason for a high risk of lightning strikes. Also in the future further lightning strikes have to be taken into consideration. In the paper a fundamental lightning protection design concept for renewable energy hybrid-systems without power mains connection and protection measures against direct strikes and overvoltages are shown in detail. The design concept was realized exemplarily for the hybrid-system VATALI. The hardware costs for the protection measures were about 15,000 €. About 50% of the costs are due to protection measures against direct strikes, 50% are due to overvoltage protection. Future extensions, new installations, or modifications have to be included into the lightning protection design concept of the hybrid-system. KW - Blitzschutz KW - Erneuerbare Energien KW - Hybridsystem KW - Lightning protection KW - Renewable energy KW - hybrid-system Y1 - 2001 ER - TY - JOUR A1 - Kern, Alexander A1 - Krichel, Frank T1 - Considerations about the lightning protection system of mains independent renewable energy hybrid-systems - practical experiences JF - Journal of electrostatics. 60 (2004), H. 2-4 Y1 - 2004 SN - 0304-3886 N1 - ISSN der E-Ausg.: 0304-3886 SP - 257 EP - 263 ER - TY - CHAP A1 - Kern, Alexander A1 - Krichel, Frank T1 - Considerations about the lightning protection system of mains independent renewable energy hybrid-systems - practical experiences N2 - In the paper a lightning protection design concept for renewable energy hybrid-systems without power mains connection is described. Based on a risk analysis protection measures against direct strikes and overvoltages are shown in an overview. The design concept is realized exemplarily for the hybrid-system VATALI on the Greek island Crete. VATALI, not lightning protected at that time, was a victim of a lightning strike in the year 2000 causing destructions and damages of some mechanical and electrical components with costs of approx. 60.000 €. The hardware costs for the protection measures were about 15.000 €: about 50% of the costs are due to protection measures against direct strikes, 50% are due to overvoltage protection. KW - Blitzschutz KW - Erneuerbare Energien KW - Hybridsystem KW - Photovoltaikanlage KW - Windenergieanlage KW - Lightning protection KW - renewable energy KW - hybrid system KW - photovoltaic system KW - wind turbine Y1 - 2002 ER - TY - JOUR A1 - Kern, Alexander A1 - Klöters, Georg A1 - Pferdemenges, Jörg T1 - Optimised protection against lightning for the signalling and safety systems of level crossings on non-electrified railway lines JF - RTR : European Rail Technology Review Y1 - 2010 SN - 0079-9548 VL - 50 IS - 2 ER - TY - CHAP A1 - Kern, Alexander A1 - Imani Vashiani, Anahita A1 - Timmermanns, Tobias T1 - Threat for human beings due to touch voltages and body currents caused by direct lightning strikes in case of non-isolated lightning protection systems using natural components T2 - 35th International Conference on Lightning Protection (ICLP) and XVI International Symposium on Lightning Protection (SIPDA) N2 - For typical cases of non-isolated lightning protection systems (LPS) the impulse currents are investigated which may flow through a human body directly touching a structural part of the LPS. Based on a basic LPS model with conventional down-conductors especially the cases of external and internal steel columns and metal façades are considered and compared. Numerical simulations of the line quantities voltages and currents in the time domain are performed with an equivalent circuit of the entire LPS. As a result it can be stated that by increasing the number of conventional down-conductors and external steel columns the threat for a human being can indeed be reduced, but not down to an acceptable limit. In case of internal steel columns used as natural down-conductors the threat can be reduced sufficiently, depending on the low-resistive connection of the steel columns to the lightning equipotential bonding or the earth termination system, resp. If a metal façade is used the threat for human beings touching is usually very low, if the façade is sufficiently interconnected and multiply connected to the lightning equipotential bonding or the earth termination system, resp. KW - Lightning protection system KW - down-conductor KW - steel columns KW - metal façade KW - touch voltage Y1 - 2021 SN - 978-1-6654-2346-5 U6 - http://dx.doi.org/10.1109/ICLPandSIPDA54065.2021.9627465 N1 - 35th International Conference on Lightning Protection (ICLP) and XVI International Symposium on Lightning Protection (SIPDA), 20-26 Sept. 2021, Colombo, Sri Lanka PB - IEEE ER - TY - JOUR A1 - Kern, Alexander A1 - Heidler, Fridolin A1 - Zischank, Wolfgang J. A1 - Frentzel, Ralf T1 - Lightning current distribution and coupling to control cables in power plants or large industrial facilites Y1 - 2002 N1 - International Conference on Grounding and Earthing <2002, Rio de Janeiro> ER - TY - CHAP A1 - Kern, Alexander A1 - Heidler, Fridolin A1 - Seevers, M. A1 - Zischank, Wolfgang J. T1 - Magnetic Fields and Induced Voltages in case of a Direct Strike - Comparison of Results obtained from Measurements at a Scaled Building to those of IEC 62305-4 N2 - In the paper the results obtained from experiments at a modelled reinforced building in case of a direct lightning strike are compared with calculations. The comparison includes peak values of the magnetic field Hmax, its derivative (dH/dt)max and of induced voltages umax in typical cable routings. The experiments are performed at a 1:6 scaled building and the results are extrapolated using the similarity relations theory. The calculations are based on the approximate formulae given in IEC 62305-4 and have to be supplemented by a rough estimation of the additional shielding effect of a second reinforcement layer. The comparison shows, that the measured peak values of the magnetic field and its derivative are mostly lower than the calculated. The induced voltages are in good agreement. Hence, calculations of the induced voltages based on IEC 62305-4 are a good method for lightning protection studies of buildings, where the reinforcement is used as a grid-like electromagnetic shield. N2 - Auswirkungen eines direkten Blitzeinschlages auf ein Gebäude, Vergleich von experimentellen Ergebnissen und Berechnungen basierend auf einer Formel aus der IEC 62305-4 KW - Blitz KW - Direkter Blitzschlag KW - Elektromagnetischer Schutzschild KW - Magnetische Felder KW - Induzierte Spannungen KW - Kalkulation KW - Direct lightning strike KW - electromagnetic shield KW - magnetic fields KW - induced voltages KW - calculations Y1 - 2004 SN - 0304-3886 N1 - Journal of electrostatics: Beitr. auf S. 379 - 385. doi:10.1016/j.elstat.2006.09.004 ER - TY - JOUR A1 - Kern, Alexander A1 - Heidler, F. A1 - Zischank, W. T1 - Induced overvoltages in cable ducts taking into account the current flow into earth / F. Heidler ; W. Zischank ... A. Kern ... JF - Conference proceedings : 14th - 18th September 1998, [Burlington Hotel, Birmingham, United Kingdom] / organised by: School of Engineering and Advanced Technology, Staffordshire University, United Kingdom Y1 - 1998 N1 - International Conference on Lightning Protection <24, 1998, Birmingham> ; School of Engineering and Advanced Technology ; ICLP <4, 1998, Birmingham> CY - Birmingham ER - TY - JOUR A1 - Kern, Alexander A1 - Frentzel, Ralf A1 - Behrens, Jörg T1 - Simulation of the transient voltages in the auxiliary power network of a large power plant in case of a direct lightning strike to the high-voltage overhead transmission line Y1 - 2010 N1 - 30th International Conference on Lightning Protection, Cagliari (Italien), 2010 SP - 749-1 EP - 749-7 ER -