TY - CHAP A1 - Kern, Alexander A1 - Krichel, Frank T1 - Considerations about the lightning protection system of mains independent renewable energy hybrid-systems - practical experiences N2 - In the paper a lightning protection design concept for renewable energy hybrid-systems without power mains connection is described. Based on a risk analysis protection measures against direct strikes and overvoltages are shown in an overview. The design concept is realized exemplarily for the hybrid-system VATALI on the Greek island Crete. VATALI, not lightning protected at that time, was a victim of a lightning strike in the year 2000 causing destructions and damages of some mechanical and electrical components with costs of approx. 60.000 €. The hardware costs for the protection measures were about 15.000 €: about 50% of the costs are due to protection measures against direct strikes, 50% are due to overvoltage protection. KW - Blitzschutz KW - Erneuerbare Energien KW - Hybridsystem KW - Photovoltaikanlage KW - Windenergieanlage KW - Lightning protection KW - renewable energy KW - hybrid system KW - photovoltaic system KW - wind turbine Y1 - 2002 ER - TY - JOUR A1 - Kern, Alexander A1 - Schelthoff, Christof A1 - Mathieu, Moritz T1 - Detaillierte Berechnung der Einfangwirksamkeiten von Fangeinrichtungen JF - Elektro-Praktiker N2 - Im Beitrag wird zunächst das Verfahren eines dynamischen elektro-geometrischen Modells vorgestellt. Dieses arbeitet im Gegensatz zum klassischen Blitzkugel-Verfahren nicht mit konstanten Radien; vielmehr wird der Radius der Blitzkugel variiert. Dabei werden ausschließlich vorhandene und in internationalen Normen anerkannte Ergebnisse, blitzphysikalische Grundlagen und Untersuchungen verwendet, und auf deren Grundlage ein numerisches Verfahren erarbeitet. Mit dem dynamischen elektro-geometrischen Modell werden dann einige Beispiele des Schutzes mit Fangstangen, die gemäß dem klassischen Blitzkugel-Verfahren nach DIN EN 62305-3 für die Schutzklassen I – II – III – IV geplant sind, untersucht. Es wird gezeigt, dass die Einfangwirksamkeiten wesentlich höher sind als in der Normenreihe DIN EN 62305 selbst angegeben. Grund dafür ist die Tatsache, dass das Blitzkugel-Verfahren sehr konservativ aufgebaut ist und dem Planer von Blitzschutzsystemen nur die möglichen Stellen für einen Einschlag aufzeigt, ohne eine Bewertung der Einschlagshäufigkeit zu liefern. Andererseits bedeutet dies jedoch, dass man mit dem klassischen Blitzkugel-Verfahren stets auf der „sicheren Seite“ liegt. Y1 - 2012 SN - 0013-5569 VL - 66 IS - 4 PB - Huss Medien CY - Berlin ER - TY - JOUR A1 - Kern, Alexander A1 - Schelthoff, Christof A1 - Mathieu, Moritz T1 - Detaillierte Berechnung der Einfangwirksamkeiten von Fangeinrichtungen mit einem dynamischen elektro-geometrischen Modell - Detailed calculation of the interception efficiencies for airtermination systems using a dynamic electro-geometrical model Y1 - 2011 N1 - 9. VDE/ABB-Blitzschutztagung, Neu-Ulm 2011 SP - 1 EP - 5 ER - TY - CHAP A1 - Surtees, A. J. A1 - Gillespie, A. A1 - Kern, Alexander A1 - Rousseau, A. T1 - DEVELOPMENT OF A RISK ASSESSMENT CALCULATOR BASED ON A SIMPLIFIED FORM OF THE IEC 62305-2 STANDARD ON LIGHTNING PROTECTION N2 - Neue Blitzschutznorm IEC 62305. Entwicklung einer einfachen Software zur Risikoabwägung N2 - IEC Technical Committee 81 is currently creating the new IEC 62305 series of standards on Lightning Protection. Working Group 9 is responsible for Part 2 of this series, which deals with the assessment and management of risk its CDV (Committee Draft for Voting) stage and has been circulated to National Committees for comment. The paper details the development of the Simplified IEC Risk Assessment Calculator software tool as described in Informative Annex J of IEC62305-2 Ed.1/CDV 2. This tool is intended as a simplified implementation of the more rigorous treatment of risk management found in the written document. It is designed to be relatively intuitive for users who wish to obtain an initial assessment of risk sensitivity, but should not be considered a substitute to a full understanding of the methods provided in the standard when dealing with more complicated structures or those where greater risks to personal or system operation are involved. KW - Risiko KW - Risikoabwägung KW - Blitzrisiko KW - Blitzschutz KW - Risk KW - Risk Management KW - Risk Assessment KW - Lightning Risk KW - Lightning Protection Y1 - 2004 ER - TY - JOUR A1 - Kern, Alexander A1 - Schelthoff, Christof A1 - Mathieu, Moritz T1 - Die dynamische Blitzkugel : Wahrscheinlichkeitsberechnung für Blitzeinschläge in Gebäude JF - De Fachzeitschrift für das Elektrohandwerk. 13-14 (2010) Y1 - 2010 SP - 24 EP - 29 ER - TY - JOUR A1 - Kern, Alexander A1 - Landers, E.-U. A1 - Scheibe, K. A1 - Zahlmann, P. T1 - Die künftige deutsche Blitzschutznormung (1) : Reihe DIN EN 62305 / VDE 0185-305-x:2006 JF - De : der Elektro- und Gebäudetechniker / Ausgabe ZV. 81 (2006), H. 15-16 Y1 - 2006 SN - 1617-1160 N1 - In der Bibliothek vorhanden: 23 Z 863 (Bibliothek Eupener Str.) SP - 26 EP - 30 ER - TY - JOUR A1 - Kern, Alexander A1 - Landers, E.-U. T1 - Die künftige deutsche Blitzschutznormung (2/3) – Reihe DIN EN 62305:2006 – Teil 2: Risikomanagement JF - De : der Elektro- und Gebäudetechniker / Ausgabe ZV. 81 (2006), H. 18 - 19 Y1 - 2006 SN - 1617-1160 ER - TY - CHAP A1 - Kern, Alexander T1 - Die neue DIN EN 62305-2 (VDE 0185-305-2) Ed.2:2013-02 - Änderungen zur Ed.l und zugehörige Beiblätter T2 - 10. VDE, VBB-Blitzschutztagung : Vorträge der 10. VDE, ABB-Fachtagung vom 24. bis 25. Oktober 2013 in Neu-Ulm. (VDE-Fachbericht ; 70) Y1 - 2013 SN - 978-3-8007-3540-2 SP - 9 EP - 16 PB - VDE-Verl. CY - Berlin ER - TY - JOUR A1 - Kern, Alexander A1 - Landers, E.-U. T1 - Die neuen Blitzschutz-Vornormen der Reihe VDE-V 0185:2002 Y1 - 2002 ER - TY - JOUR A1 - Kern, Alexander T1 - Die neuen Blitzschutznormen der Reihe DIN EN 62305 (VDE 0185-305-x) JF - ETZ : Elektrotechnik + Automation. 2006 (2006), H. 2 Y1 - 2006 SN - 0170-1711 N1 - 2. ISSN: 0948-7387 ; In der Bibliothek unter 23 Z 133 (Eupener Str.) und 63 ZS 035 (Jülich) vorhanden. SP - 42 EP - 45 ER -