TY - CHAP A1 - Kern, Alexander A1 - Imani Vashiani, Anahita A1 - Timmermanns, Tobias T1 - Threat for human beings due to touch voltages and body currents caused by direct lightning strikes in case of non-isolated lightning protection systems using natural components T2 - 35th International Conference on Lightning Protection (ICLP) and XVI International Symposium on Lightning Protection (SIPDA) N2 - For typical cases of non-isolated lightning protection systems (LPS) the impulse currents are investigated which may flow through a human body directly touching a structural part of the LPS. Based on a basic LPS model with conventional down-conductors especially the cases of external and internal steel columns and metal façades are considered and compared. Numerical simulations of the line quantities voltages and currents in the time domain are performed with an equivalent circuit of the entire LPS. As a result it can be stated that by increasing the number of conventional down-conductors and external steel columns the threat for a human being can indeed be reduced, but not down to an acceptable limit. In case of internal steel columns used as natural down-conductors the threat can be reduced sufficiently, depending on the low-resistive connection of the steel columns to the lightning equipotential bonding or the earth termination system, resp. If a metal façade is used the threat for human beings touching is usually very low, if the façade is sufficiently interconnected and multiply connected to the lightning equipotential bonding or the earth termination system, resp. KW - Lightning protection system KW - down-conductor KW - steel columns KW - metal façade KW - touch voltage Y1 - 2021 SN - 978-1-6654-2346-5 U6 - http://dx.doi.org/10.1109/ICLPandSIPDA54065.2021.9627465 N1 - 35th International Conference on Lightning Protection (ICLP) and XVI International Symposium on Lightning Protection (SIPDA), 20-26 Sept. 2021, Colombo, Sri Lanka PB - IEEE ER - TY - CHAP A1 - Birkl, Josef A1 - Diendorfer, Gerhard A1 - Kern, Alexander A1 - Thern, Stephan T1 - Extremely high lightning peak currents T2 - 34th International Conference on Ligntning Protection, 02-07 September 2018 Y1 - 2018 SN - 978-1-5386-6635-7 ER - TY - JOUR A1 - Birkl, Josef A1 - Diendorfer, Gerhard A1 - Kern, Alexander A1 - Thern, Stephan T1 - Extrem hohe Blitzströme JF - Elektropraktiker N2 - Blitze sind nach wie vor eine enorme Schadensquelle für Personenschäden, Brände, mechanische Zerstörungen und insbesondere auch Überspannungen. Das zeigen nicht zuletzt aktuelle Statistiken der Schadensversicherer. Immer wieder gibt es Meldungen über extrem hohe Blitzströme, die natürlich auch zu großen Schäden und Zerstörungen führen können. Dabei werden Scheitelwerte von teilweise deutlich über 300 kA genannt. Dies wirft Fragen auf, da die „klassische“ Blitzstatistik (z. B. nach CIGRE und IEC [8][10]) bisher solche Werte nicht kennt. Diese extremen Blitzströme werden meist aus den Daten von Blitzortungssystemen ermittelt. Y1 - 2018 VL - 72 IS - 3 SP - 217 EP - 225 PB - Huss Medien CY - Berlin ER - TY - CHAP A1 - Kern, Alexander T1 - Optimierung des Blitzschutzes bei Biogasanlagen T1 - Improvement of lightning protection for biogas plants T2 - 12. VDE/ABB-Blitzschutztagung : Beiträge der 12. VDE/ABB-Fachtagung, 12.-13. Oktober 2017, Aschaffenburg Y1 - 2017 SN - 978-3-8007-4459-6 SP - 48 EP - 56 ER - TY - CHAP A1 - Kern, Alexander A1 - Brocke, Ralph T1 - Planung von Fangeinrichtungen mit dem dynamischen elektro-geometrischen Modell - Mögliche praktische Anwendungen T1 - Design of air-terminations using the dynamic electro-geometrical model - Possible practical applications T2 - 12. VDE/ABB-Blitzschutztagung : Beiträge der 12. VDE/ABB-Fachtagung, 12.-13. Oktober 2017, Aschaffenburg Y1 - 2017 SN - 978-3-8007-4459-6 SP - 75 EP - 82 ER - TY - CHAP A1 - Birkl, Josef A1 - Diendorfer, Gerhard A1 - Kern, Alexander A1 - Thern, Stephan T1 - Extrem hohe Blitzströme T1 - Extremly high lightning currents T2 - 12. VDE/ABB-Blitzschutztagung : Beiträge der 12. VDE/ABB-Fachtagung, 12.-13. Oktober 2017, Aschaffenburg Y1 - 2017 SN - 978-3-8007-4459-6 SP - 146 EP - 152 ER - TY - JOUR A1 - Kern, Alexander T1 - Blitz- und Überspannungsschutz von Kernkraftwerken - Nachweisführung der ausreichenden Sicherheit für leittechnische Einrichtungen auch bei Blitzeinschlägen mit extremen Parametern JF - Atw. International Journal for Nuclear Power N2 - Für das Auftreten extremer Wetterereignisse werden für Kernkraftwerke Eintrittshäufigkeiten für nicht mehr beherrschbare Zustände von unter 10⁻⁴/a gefordert. Dies gilt auch für die Einwirkung von Blitzeinschlägen. Die bisherige Nachweisführung zu Blitz- und Überspannungsschutz eines KKW in Deutschland ist deterministisch. In diesem Bericht werden das Vorgehen für einen entsprechenden Nachweis für leittechnische Einrichtungen der Sicherheitstechnik von KKW, der zur geforderten Zielgröße der Eintrittshäufigkeit führt. Die Ergebnisse werden zusammenfassend bewertet. Y1 - 2016 SN - 1431-5254 VL - 61 IS - 8/9 SP - 534 EP - 543 PB - Inforum CY - Berlin ER - TY - BOOK A1 - Kern, Alexander A1 - Wettingfeld, Jürgen T1 - Blitzschutzsysteme 2 : Schutz für besondere bauliche Anlagen ; Schutz für elektrische und elektronische Systeme in baulichen Anlagen ; Erläuterungen zu den Normen DIN EN 62305-3 (VDE 0185-305-3):2011-10, DIN EN 62305-4 (VDE 0185-305-4):2011-10. (VDE-Schriftenreihe Normen verständlich ; 160) Y1 - 2015 SN - 978-3-8007-3653-9 PB - VDE-Verl. CY - Berlin [u.a.] ER - TY - CHAP A1 - Wetter, Martin A1 - Kern, Alexander T1 - Number of lightning strikes to tall structures - comparison of calculations and measurements using a modern lightning monitoring system T2 - 2014 International Conference on Lightning Protection (ICLP), Shanghai, China Y1 - 2014 SP - 1 EP - 7 ER - TY - BOOK A1 - Kern, Alexander A1 - Wettingfeld, Jürgen T1 - Blitzschutzsysteme 1 : allgemeine Grundsätze, Risikomanagement, Schutz von baulichen Anlagen und Personen ; Erläuterungen zu den Normen DIN EN 62305-1 (VDE 0185-305-1):2011-10, DIN EN 62305-2 (VDE 0185-305-2):2013-02, DIN EN 62305-3 (VDE 0185-305-3):2011-10. (VDE-Schriftenreihe Normen verständlich ; 44) Y1 - 2014 SN - 978-3-8007-3511-2 PB - VDE-Verl. CY - Berlin [u.a.] ER - TY - CHAP A1 - Rousseau, Alain A1 - Kern, Alexander T1 - How to deal with environmental risk in IEC 62305-2 T2 - 2014 International Conference on Lightning Protection (ICLP), Shanghai, China N2 - The 2nd edition of the lightning risk management standard (IEC 62305-2) considers structures, which may endanger environment. In these cases, the loss is not limited to the structure itself, which is valid for usual structures. In the past (Edition 1) this danger was simply taken into account by a special hazard factor, multiplying the existing risk for the structure with a number. Now, in the edition 2, we add to the risk for the structure itself a “second risk” due to the losses outside the structure. The losses outside can be treated independently from what occurs inside. This is a major advantage to analyze the risk for sensitive structures, like chemical plants, nuclear plants, or structures containing explosives, etc. In this paper, the existing procedure given by the European version EN 62305-2 Ed.2 is further developed and applied to a few structures. Y1 - 2014 SP - 521 EP - 527 ER - TY - CHAP A1 - Kern, Alexander A1 - Braun, Christian T1 - Risk management according to IEC 62305-2 edition 2: 2010–12 assessment of structures with a risk of explosion T2 - 2014 International Conference on Lightning Protection (ICLP), Shanghai, China N2 - Risk management for structures with a risk of explosion should be considered very carefully when performing a risk analysis according to IEC 62305-2. In contrast to the 2006 edition of the standard, the 2010 edition describes the topic “Structures with a risk of explosion” in more detail. Moreover, in Germany separate procedures and parameters are defined for the risk analysis of structures with a risk of explosion (Supplement 3 of the German DIN EN 62305-2 standard). This paper describes the contents and the relevant calculations of this Supplement 3, together with a numerical example. Y1 - 2014 SP - 1237 EP - 1242 ER - TY - JOUR A1 - Kern, Alexander A1 - Braun, Christian T1 - Neuerungen bei der Blitzschutznorm. Teil 2 JF - etz Elektrotechnik und Automation Y1 - 2013 SN - 0170-1711 N1 - Printausg. in der Bibliothek der FH Aachen vorhanden: 23 Z 133 ; 63 ZS 035 VL - Bd. 134 IS - H. 8 SP - 66 EP - 69 PB - VDE-Verlag CY - Wuppertal ER - TY - CHAP A1 - Kern, Alexander T1 - Die neue DIN EN 62305-2 (VDE 0185-305-2) Ed.2:2013-02 - Änderungen zur Ed.l und zugehörige Beiblätter T2 - 10. VDE, VBB-Blitzschutztagung : Vorträge der 10. VDE, ABB-Fachtagung vom 24. bis 25. Oktober 2013 in Neu-Ulm. (VDE-Fachbericht ; 70) Y1 - 2013 SN - 978-3-8007-3540-2 SP - 9 EP - 16 PB - VDE-Verl. CY - Berlin ER - TY - CHAP A1 - Scheibe, K. A1 - Kern, Alexander T1 - Stand der Normung für Überspannungsschutzgeräte T2 - 10. VDE, VBB-Blitzschutztagung : Vorträge der 10. VDE, ABB-Fachtagung vom 24. bis 25. Oktober 2013 in Neu-Ulm. (VDE-Fachbericht ; 70) Y1 - 2013 SN - 978-3-8007-3540-2 SP - 23 EP - 27 PB - VDE-Verl. CY - Berlin ER - TY - JOUR A1 - Kern, Alexander A1 - Schelthoff, Christof A1 - Mathieu, Moritz T1 - Detaillierte Berechnung der Einfangwirksamkeiten von Fangeinrichtungen JF - Elektro-Praktiker N2 - Im Beitrag wird zunächst das Verfahren eines dynamischen elektro-geometrischen Modells vorgestellt. Dieses arbeitet im Gegensatz zum klassischen Blitzkugel-Verfahren nicht mit konstanten Radien; vielmehr wird der Radius der Blitzkugel variiert. Dabei werden ausschließlich vorhandene und in internationalen Normen anerkannte Ergebnisse, blitzphysikalische Grundlagen und Untersuchungen verwendet, und auf deren Grundlage ein numerisches Verfahren erarbeitet. Mit dem dynamischen elektro-geometrischen Modell werden dann einige Beispiele des Schutzes mit Fangstangen, die gemäß dem klassischen Blitzkugel-Verfahren nach DIN EN 62305-3 für die Schutzklassen I – II – III – IV geplant sind, untersucht. Es wird gezeigt, dass die Einfangwirksamkeiten wesentlich höher sind als in der Normenreihe DIN EN 62305 selbst angegeben. Grund dafür ist die Tatsache, dass das Blitzkugel-Verfahren sehr konservativ aufgebaut ist und dem Planer von Blitzschutzsystemen nur die möglichen Stellen für einen Einschlag aufzeigt, ohne eine Bewertung der Einschlagshäufigkeit zu liefern. Andererseits bedeutet dies jedoch, dass man mit dem klassischen Blitzkugel-Verfahren stets auf der „sicheren Seite“ liegt. Y1 - 2012 SN - 0013-5569 VL - 66 IS - 4 PB - Huss Medien CY - Berlin ER - TY - CHAP A1 - Kern, Alexander A1 - Schelthoff, Christof A1 - Mathieu, Moritz T1 - Calculation of interception efficiencies for mesh-type air-terminations according to IEC 62305-3 using a dynamic electro-geometrical model T2 - International Conference on Lightning Protection (ICLP) : 2 - 7 Sept. 2012, Vienna Y1 - 2012 SN - 978-1-4673-1896-9 (E-Book) ; 978-1-4673-1898-3 (Print) SP - 1 EP - 6 PB - IEEE CY - Piscataway, NJ ER - TY - CHAP A1 - Lo Piparo, G. B. A1 - Kern, Alexander A1 - Mazzetti, C. T1 - Some masterpoints about risk due to lightning T2 - International Conference on Lightning Protection (ICLP) : 2 - 7 Sept. 2012, Vienna Y1 - 2012 SN - 978-1-4673-1896-9 (E-Book) ; 978-1-4673-1898-3 (Print) SP - 1 EP - 6 PB - IEEE CY - Piscataway, NJ ER - TY - JOUR A1 - Scheibe, Klaus A1 - Kern, Alexander T1 - Aktueller Stand der Normung zum Überspannungschutz JF - 9. VDE/ABB-Blitzschutztagung : Vorträge der 9. VDE/ABB-Fachtagung vom 27. bis 28. Oktober 2011 in Neu-Ulm / Veranst.: Ausschuss für Blitzschutz und Blitzforschung (ABB) im VDE Verband der Elektrotechnik Elektronik Informationstechnik e.V. Wiss. Tagungsleitung: K. Stimper Y1 - 2011 SN - 978-3-8007-3380-4 N1 - VDE/ABB-Blitzschutztagung ; (9 ; 2011.10.27-28 ; Neu-Ulm) SP - 13 EP - 17 PB - VDE-Verl. CY - Berlin ER - TY - JOUR A1 - Kern, Alexander A1 - Schelthoff, Christof A1 - Mathieu, Moritz T1 - Detaillierte Berechnung der Einfangwirksamkeiten von Fangeinrichtungen mit einem dynamischen elektro-geometrischen Modell - Detailed calculation of the interception efficiencies for airtermination systems using a dynamic electro-geometrical model Y1 - 2011 N1 - 9. VDE/ABB-Blitzschutztagung, Neu-Ulm 2011 SP - 1 EP - 5 ER - TY - JOUR A1 - Kern, Alexander A1 - Schelthoff, Christof A1 - Mathieu, Moritz T1 - Calculation of interception efficiencies for airterminations using a dynamic electro-geometrical model Y1 - 2011 N1 - XI International Symposium on Lightning Protection (SIPDA), Fortaleza (Brasilien), 2011. SP - 1 EP - 6 PB - IEEE CY - New York ER - TY - JOUR A1 - Landers, Ernst Ulrich A1 - Kern, Alexander T1 - Future evolution of risk management for structures : Advancement for the future IEC 62305-2 Ed3 Y1 - 2011 N1 - XI International Symposium on Lightning Protection (SIPDA), Fortaleza (Brasilien), 2011. SP - 1 EP - 6 PB - IEEE CY - New York ER - TY - JOUR A1 - Kern, Alexander A1 - Schelthoff, Christof A1 - Mathieu, Moritz T1 - Probability of lightning strikes to air-terminations of structures using the electro-geometrical model theory and the statistics of lightning current parameters JF - Atmospheric Research. 104 (2011) Y1 - 2011 SN - 0169-8095 N1 - Article in Press PB - Elsevier CY - Amsterdam ER - TY - JOUR A1 - Kern, Alexander A1 - Scheibe, Klaus T1 - Die neuen internationalen Blitzschutz-Standards der Reihe IEC 62305:2010 : Überblick und Stand der Umsetzung in die nationale Normenreihe DIN EN 62305 JF - 9. VDE/ABB-Blitzschutztagung : Vorträge der 9. VDE/ABB-Fachtagung vom 27. bis 28. Oktober 2011 in Neu-Ulm / Veranst.: Ausschuss für Blitzschutz und Blitzforschung (ABB) im VDE Verband der Elektrotechnik Elektronik Informationstechnik e.V. Wiss. Tagungsleitung: K. Stimper Y1 - 2011 SN - 978-3-8007-3380-4 N1 - VDE/ABB-Blitzschutztagung ; (9 ; 2011.10.27-28 ; Neu-Ulm) SP - 7 EP - 12 PB - VDE-Verl. CY - Berlin ER - TY - JOUR A1 - Bouquegneau, Christian A1 - Kern, Alexander A1 - Rousseau, Alain T1 - Lightning safety guidelines Y1 - 2010 N1 - Ground´2010 International Conference on Grounding and Earthing ; 4th International Conference ond Lightning Physics and Effects, Nov. 2010 Salvador - Brazil SP - 1 EP - 6 ER - TY - JOUR A1 - Kern, Alexander A1 - Frentzel, Ralf A1 - Behrens, Jörg T1 - Simulation of the transient voltages in the auxiliary power network of a large power plant in case of a direct lightning strike to the high-voltage overhead transmission line Y1 - 2010 N1 - 30th International Conference on Lightning Protection, Cagliari (Italien), 2010 SP - 749-1 EP - 749-7 ER - TY - JOUR A1 - Kern, Alexander A1 - Klöters, Georg A1 - Pferdemenges, Jörg T1 - Optimised protection against lightning for the signalling and safety systems of level crossings on non-electrified railway lines JF - RTR : European Rail Technology Review Y1 - 2010 SN - 0079-9548 VL - 50 IS - 2 ER - TY - JOUR A1 - Kern, Alexander A1 - Schelthoff, Christof A1 - Mathieu, Moritz T1 - Die dynamische Blitzkugel : Wahrscheinlichkeitsberechnung für Blitzeinschläge in Gebäude JF - De Fachzeitschrift für das Elektrohandwerk. 13-14 (2010) Y1 - 2010 SP - 24 EP - 29 ER - TY - JOUR A1 - Kern, Alexander A1 - Schelthoff, Christof A1 - Mathieu, Moritz T1 - Probability of lightning strikes to air-terminations of structures using the electro-geometrical model theory and the statistics of lightning current parameters Y1 - 2010 N1 - 30th International Conference on Lightning Protection, Cagliari (Italien), 2010 SP - 750-1 EP - 750-8 ER - TY - CHAP A1 - Kern, Alexander A1 - Dikta, Gerhard T1 - Probability of damage of electrical and electronic systems due to indirect lightning flashes - investigation of data from German insurance companies N2 - In the presented paper data collected from the field related to damage statistics of electrical and electronic apparatus in household are reported and investigated. These damages (total number approx. 74000 cases), registered by five German insurance companies in 2005 and 2006, were adviced by customers as caused by lightning overvoltages. With the use of stochastical methods it is possible, to reasses the collected data and to distinguish between cases, which are with high probability caused by lightning overvoltages, and those, which are not. If there was an indication for a direct strike, this case was excluded, so the focus was only on indirect lightning flashes, i.e. only flashes to ground near the structure and flashes to or nearby an incoming service line were investigated. The data from the field contain the location of damaged apparatus (residence of the policy holder) and the distances of the nearest cloud-to-ground stroke to the location of the damage registered by the German lightning location network BLIDS at the date of damage. The statistical data along with some complementary numerical simulations allow to verify the correspondence of the Standards rules used for IEC 62305-2 with the field data and to define some correction needs. The results could lead to a better understanding whether a damage reported to an insurance company is really caused by indirect lightning, or not. KW - Blitzschutz KW - lightning flash Y1 - 2009 ER - TY - JOUR A1 - Wettingfeld, Jürgen A1 - Kern, Alexander A1 - Krämer, Heinz-Josef A1 - Thormählen, Reyno T1 - International anerkannte Blitzschutznormen : Ausgewogener und sicherer Schutz N2 - Die Einleitung zur Norm DIN EN 62305-3 beschreibt klar und ein - deutig: Der vorliegende Teil der IEC 62305 behandelt den Schutz von baulichen Anlagen gegen materielle Schäden und den Schutz von Personen gegen Verletzungen durch Berührungs- und Schrittspannungen. Als das wesentlichste und effektivste Mittel zum Schutz von baulichen Anlagen gegen materielle Schäden gilt das Blitz - schutzsystem (LPS). KW - Blitzschutz KW - lightning protection Y1 - 2009 PB - Fachhochschule Aachen CY - Aachen ER - TY - CHAP A1 - Kern, Alexander A1 - Beierl, Ottmar A1 - Zischank, Wolfgang T1 - Calculation of the separation distance according to IEC 62305-3: 2006-10 - Remarks for the application and simplified methods N2 - [Paper of the X International Symposium on Lightning Protection 9th - 13th November, 2009 - Curitiba, Brazil. 6 pages] The international standard IEC 62305-3, published in 2006, requires as an integral part of the lightning protection system (LPS) the consideration of a separation distance between the conductors of the LPS and metal and electrical installations inside the structure to be protected. IEC 62305-3 gives two different methods for this calculation: a standard, simplified approach and a more detailed approach, which differ especially regarding the treatment of the current sharing effect on the LPS conductors. Hence, different results for the separation distance are possible, leading to some discrepancies in the use of the standard. The standard approach defined in the main part (Clause 6.3) and in Annex C of the standard in some cases may lead to a severe oversizing of the required separation distance. The detailed approach described in Annex E naturally gives more correct results. However, a calculation of the current sharing amongst all parts of the air-termination and downconductor network is necessary, in many cases requiring the use of network analysis programs. In this paper simplified methods for the assessment of the current sharing are presented, which are easy to use as well as sufficiently adequate. KW - Blitzschutz KW - Lightning protection Y1 - 2009 N1 - Paper in: [10. International Symposium on Lightning Protection 9. 13. November 2009, Curitiba, Brasilien. 6 Seiten] ER - TY - CHAP A1 - Behrens, Jörg A1 - Frentzel, Ralf A1 - Kern, Alexander T1 - Simulation der transienten Spannungsverläufe im Eigenbedarfsnetz eines Großkraftwerks bei einem kraftwerksnahen Blitzeinschlag in die Hochspannungs-Freileitung T1 - Simulation of transient voltage curve of a house-load operation net-work of large power plant by a lightning strike in a high-voltage over-head line closed to the power plant N2 - 8. VDE/ABB-Blitzschutztagung, 29. - 30. Oktober 2009 in Neu-Ulm. Blitzschutztagung <8, 2009, Neu-Ulm> Berlin : VDE Verl. 2009 Großkraftwerke können durch Blitzentladungen mit potentiellen Auswirkungen auf deren Verfügbarkeit und Sicherheit gefährdet werden. Ein sehr spezielles Szenario, welches aus aktuellem Anlass zu untersuchen war, betrifft den kraftwerksnahen Blitzeinschlag in die Hochspannungs-Freileitung am Netzanschluss der Anlage. Wird nun noch ein sogenannter Schirmfehler unterstellt, d.h. der direkte Blitzeinschlag erfolgt in ein Leiterseil des Hoch- bzw. Höchstspannungsnetzes und nicht in das darüber gespannte Erdseil, so bedeutet dies eine extreme elektromagnetische Einwirkung. Der vorliegende Beitrag befasst sich mit der Simulation eines solchen Blitzeinschlages und dessen Auswirkungen auf den Netzanschluss und die Komponenten der elektrischen Eigenbedarfsanlagen eines Kraftwerks auf den unterlagerten Spannungsebenen. Die dabei gewonnenen Erkenntnisse lassen sich ohne Einschränkungen auf Industrieanlagen mit Mittelspannungs-Netzanschluss und ohne eigener Stromversorgung übertragen. N2 - Lightning discharge can endanger large power plants with potential influence on their availability and reliability. A very special scenario, which was currently to analyse, is the lightning strike close to the high-voltage overhead line at the grid of the power plant. Supposing a failure of shielding and that the lightning strike goes directly into the line then the elec-tromagnetic effect is extremely high. The following article gives attention to the simulation of lightning strike and their effects to the connection with the grid and the components of the house-load operation of a large power plant especially to the lower voltage level sections. These results are transferable to industrial plants which have no own power supply. KW - Blitzschutz KW - Blitzeinschlag KW - lightning strike Y1 - 2009 SN - 978-3-8007-3197-8 ER - TY - JOUR A1 - Kern, Alexander A1 - Klöters, Georg A1 - Pferdmenges, Jörg T1 - Blitzschutzoptimierung in der LST an nicht-elektrifizierten Strecken JF - Signal und Draht. 101 (2009), H. 4 Y1 - 2009 SN - 0037-4997 SP - 17 EP - 21 PB - DVV Media Group CY - Hamburg ER - TY - JOUR A1 - Kern, Alexander A1 - Beierl, O. A1 - Zischank, W. T1 - DIN EN 62 305-3 - Berechnung des Trennungsabstands (Anmerkungen zur Anwendung der Berechnungsverfahren und vereinfachte Verfahren zur Abschätzung der Stromaufteilung) / Kern, A. ; Beierl, O. ; Zischank, W. JF - Elektropraktiker. 63 (2009), H. 3 Y1 - 2009 SN - 0013-5569 SP - 218 EP - 222 PB - HUSS-MEDIEN GmbH CY - Berlin ER - TY - JOUR A1 - Kern, Alexander T1 - Überarbeitung der Blitzschutznorm IEC 62305 JF - Elektropraktiker. 63 (2009), H. 4 Y1 - 2009 SN - 0013-5569 SP - 391 EP - 394 ER - TY - JOUR A1 - Kern, Alexander A1 - Dikta, Gerhard T1 - Bewerten von Schäden durch Blitzeinwirkungen JF - Elektropraktiker. 62 (2008), H. 4 Y1 - 2008 SN - 0013-5569 SP - 338 EP - 342 ER - TY - JOUR A1 - Kern, Alexander T1 - Neue deutsche Blitzschutz-Normung. Reihe DIN EN 62305 / VDE 01 85-305-x:2006 JF - Der Eisenbahningenieur. 58 (2007), H. 8 Y1 - 2007 SN - 0013-2810 N1 - in der Bereichsbibliothek Bayernallee vorhanden SP - 18 EP - 22 ER - TY - JOUR A1 - Kern, Alexander A1 - Schelthoff, Christof T1 - Auswahl von Blitzschutzmassnahmen nach DIN EN 623305 (VDE 0185-305-x) JF - etz Elektrotechnik und Automation. 127 (2007), H. 8 Y1 - 2007 SN - 0948-7387 N1 - in der Bibliothek unter den Signaturen : 23 Z 133 und 63 ZS 035 vorhanden SP - 83 EP - 90 ER - TY - JOUR A1 - Kern, Alexander A1 - Schelthoff, Christof T1 - Trennungsabstand bei Blitzschutzsystemen. Die Anforderungen nach VDE 0185-305-3:2006:10 JF - de- Der Elektro- und Gebäudetechniker (2007) Y1 - 2007 SP - 43 EP - 48 ER - TY - JOUR A1 - Kern, Alexander A1 - Zischank, Wolfgang A1 - Beierl, Ottmar T1 - Anmerkungen zur Berechnung des Trennungsabstands nach DIN EN 62305-3 (VDE 0185-305-3): 2006-10 / Zischank, Wolfgang ; Beierl, Ottmar ; Kern, Alexander JF - 7. VDE-ABB-Blitzschutztagung : Vorträge der VDE-ABB-Fachtagung vom 15. bis 16. November 2007 in Neu-Ulm / Veranst.: Ausschuss für Blitzschutz und Blitzforschung (ABB) im VDE, Verband der Elektrotechnik, Elektronik, Informationstechnik e.V. Wiss. Tagungsltg.: K. Stimper Y1 - 2007 SN - 978-3-8007-3062-9 N1 - VDE-Fachbericht ; 64 ; Blitzschutztagung <7, 2007, Neu-Ulm> SP - 1 EP - 8 PB - VDE-Verl. CY - Berlin ER - TY - JOUR A1 - Kern, Alexander A1 - Dikta, Gerhard A1 - Krichel, Frank T1 - Zur Wahrscheinlichkeit für Schäden an elektrischen und elektronischen Einrichtungen durch indirekte Blitzeinschläge - Auswertung von Schadensstatistiken, analytischen und numerischen Berechnungen JF - 7. VDE-ABB-Blitzschutztagung : Vorträge der VDE-ABB-Fachtagung vom 15. bis 16. November 2007 in Neu-Ulm / Veranst.: Ausschuss für Blitzschutz und Blitzforschung (ABB) im VDE, Verband der Elektrotechnik, Elektronik, Informationstechnik e.V. Wiss. Tagungsltg.: K. Stimper Y1 - 2007 SN - 978-3-8007-3062-9 N1 - VDE-Fachbericht ; 64 ; Blitzschutztagung <7, 2007, Neu-Ulm> SP - 1 EP - 9 PB - VDE-Verl. CY - Berlin ER - TY - JOUR A1 - Kern, Alexander A1 - Landers, E.-U. A1 - Scheibe, K. A1 - Zahlmann, P. T1 - Die künftige deutsche Blitzschutznormung (1) : Reihe DIN EN 62305 / VDE 0185-305-x:2006 JF - De : der Elektro- und Gebäudetechniker / Ausgabe ZV. 81 (2006), H. 15-16 Y1 - 2006 SN - 1617-1160 N1 - In der Bibliothek vorhanden: 23 Z 863 (Bibliothek Eupener Str.) SP - 26 EP - 30 ER - TY - JOUR A1 - Kern, Alexander T1 - Die neuen Blitzschutznormen der Reihe DIN EN 62305 (VDE 0185-305-x) JF - ETZ : Elektrotechnik + Automation. 2006 (2006), H. 2 Y1 - 2006 SN - 0170-1711 N1 - 2. ISSN: 0948-7387 ; In der Bibliothek unter 23 Z 133 (Eupener Str.) und 63 ZS 035 (Jülich) vorhanden. SP - 42 EP - 45 ER - TY - JOUR A1 - Kern, Alexander A1 - Landers, E.-U. T1 - Die künftige deutsche Blitzschutznormung (2/3) – Reihe DIN EN 62305:2006 – Teil 2: Risikomanagement JF - De : der Elektro- und Gebäudetechniker / Ausgabe ZV. 81 (2006), H. 18 - 19 Y1 - 2006 SN - 1617-1160 ER - TY - JOUR A1 - Kern, Alexander A1 - Krichel, Frank T1 - Considerations about the lightning protection system of mains independent renewable energy hybrid-systems - practical experiences JF - Journal of electrostatics. 60 (2004), H. 2-4 Y1 - 2004 SN - 0304-3886 N1 - ISSN der E-Ausg.: 0304-3886 SP - 257 EP - 263 ER - TY - BOOK A1 - Kern, Alexander T1 - Blitz- und Überspannungsschutz für Anlagen der regenerativen Energietechnik Y1 - 2004 PB - Fachhochschule Aachen, Abt. Jülich CY - Aachen ER - TY - JOUR A1 - Zischank, Wolfgang J. A1 - Heidler, Fridolin A1 - Wiesinger, J. A1 - Metwally, I. A1 - Kern, Alexander A1 - Seevers, M. T1 - Laboratory simulation of direct lightning strokes to a modeled building : measurement of magnetic fields and included voltages JF - Journal of electrostatics. 60 (2004), H. 2 - 4 Y1 - 2004 SN - 0304-3886 N1 - ISSN der E-Ausg.: 0304-3886 SP - 223 EP - 232 ER - TY - CHAP A1 - Surtees, A. J. A1 - Gillespie, A. A1 - Kern, Alexander A1 - Rousseau, A. T1 - DEVELOPMENT OF A RISK ASSESSMENT CALCULATOR BASED ON A SIMPLIFIED FORM OF THE IEC 62305-2 STANDARD ON LIGHTNING PROTECTION N2 - Neue Blitzschutznorm IEC 62305. Entwicklung einer einfachen Software zur Risikoabwägung N2 - IEC Technical Committee 81 is currently creating the new IEC 62305 series of standards on Lightning Protection. Working Group 9 is responsible for Part 2 of this series, which deals with the assessment and management of risk its CDV (Committee Draft for Voting) stage and has been circulated to National Committees for comment. The paper details the development of the Simplified IEC Risk Assessment Calculator software tool as described in Informative Annex J of IEC62305-2 Ed.1/CDV 2. This tool is intended as a simplified implementation of the more rigorous treatment of risk management found in the written document. It is designed to be relatively intuitive for users who wish to obtain an initial assessment of risk sensitivity, but should not be considered a substitute to a full understanding of the methods provided in the standard when dealing with more complicated structures or those where greater risks to personal or system operation are involved. KW - Risiko KW - Risikoabwägung KW - Blitzrisiko KW - Blitzschutz KW - Risk KW - Risk Management KW - Risk Assessment KW - Lightning Risk KW - Lightning Protection Y1 - 2004 ER - TY - CHAP A1 - Kern, Alexander A1 - Heidler, Fridolin A1 - Seevers, M. A1 - Zischank, Wolfgang J. T1 - Magnetic Fields and Induced Voltages in case of a Direct Strike - Comparison of Results obtained from Measurements at a Scaled Building to those of IEC 62305-4 N2 - In the paper the results obtained from experiments at a modelled reinforced building in case of a direct lightning strike are compared with calculations. The comparison includes peak values of the magnetic field Hmax, its derivative (dH/dt)max and of induced voltages umax in typical cable routings. The experiments are performed at a 1:6 scaled building and the results are extrapolated using the similarity relations theory. The calculations are based on the approximate formulae given in IEC 62305-4 and have to be supplemented by a rough estimation of the additional shielding effect of a second reinforcement layer. The comparison shows, that the measured peak values of the magnetic field and its derivative are mostly lower than the calculated. The induced voltages are in good agreement. Hence, calculations of the induced voltages based on IEC 62305-4 are a good method for lightning protection studies of buildings, where the reinforcement is used as a grid-like electromagnetic shield. N2 - Auswirkungen eines direkten Blitzeinschlages auf ein Gebäude, Vergleich von experimentellen Ergebnissen und Berechnungen basierend auf einer Formel aus der IEC 62305-4 KW - Blitz KW - Direkter Blitzschlag KW - Elektromagnetischer Schutzschild KW - Magnetische Felder KW - Induzierte Spannungen KW - Kalkulation KW - Direct lightning strike KW - electromagnetic shield KW - magnetic fields KW - induced voltages KW - calculations Y1 - 2004 SN - 0304-3886 N1 - Journal of electrostatics: Beitr. auf S. 379 - 385. doi:10.1016/j.elstat.2006.09.004 ER -