• search hit 1 of 2
Back to Result List

Lightning protection design of a renewable energy hybrid-system without power mains connection

  • In the year 2000 a direct lightning strike to the hybridsystem without power mains connection VATALI on the Greek island Crete results in the destruction and damage of some mechanical and electrical components. The hybrid-system VATALI was not lightning protected at that time. The hardware damage costs are approx. 60,000 €. The exposed site of the hybrid-system on top of a mountain was and still is the reason for a high risk of lightning strikes. Also in the future further lightning strikes have to be taken into consideration. In the paper a fundamental lightning protection design concept for renewable energy hybrid-systems without power mains connection and protection measures against direct strikes and overvoltages are shown in detail. The design concept was realized exemplarily for the hybrid-system VATALI. The hardware costs for the protection measures were about 15,000 €. About 50% of the costs are due to protection measures against direct strikes, 50% are due to overvoltage protection. Future extensions, new installations, or modifications have to be included into the lightning protection design concept of the hybrid-system.

Download full text files

Export metadata

Additional Services

Share in Twitter Search Google Scholar
Metadaten
Author:Alexander Kern, Frank Krichel, Klaus-Peter Müller
DOI:https://doi.org/10.21269/13
Document Type:Conference Proceeding
Language:English
Year of Completion:2001
Publishing Institution:Fachhochschule Aachen
Contributing Corporation:International Conference on Lightning and Static Electricity <2001, Seattle>
Date of the Publication (Server):2005/06/07
Tag:Blitzschutz; Erneuerbare Energien; Hybridsystem
Lightning protection; Renewable energy; hybrid-system
Institutes:FH Aachen / Fachbereich Energietechnik
Dewey Decimal Classification:6 Technik, Medizin, angewandte Wissenschaften / 60 Technik / 600 Technik, Technologie