Simulation of the transient voltages in the auxiliary power network of a large power plant in case of a direct lightning strike to the high-voltage overhead transmission line

  • Large power plants can be endangered by lightning strikes with possible consequences regarding their safety and availability. A special scenario is a lightning strike to the HV overhead transmission line close to the power plant's connection to the power grid. If then additionally a so-called shielding failure of the overhead ground wire on top of the overhead transmission line is assumed, i.e. the lightning strikes directly into a phase conductor, this is an extreme electromagnetic disturbance. The paper deals with the numerical simulation of such a lightning strike and the consequences on the components of the power plant's auxiliary power network connected to different voltage levels.

Export metadata

Additional Services

Share in X Search Google Scholar
Metadaten
Author:Alexander Kern, Ralf Frentzel, Jörg Behrens
DOI:https://doi.org/10.1109/ICLP.2010.7845756
ISBN:978-88-905519-0-1
Publisher:IEEE
Place of publication:New York
Document Type:Article
Language:English
Year of Completion:2010
Date of the Publication (Server):2012/12/18
Tag:arresters; conductors; lightning; power generation; power transmission lines; surges
First Page:749-1
Last Page:749-7
Note:
2010 30th International Conference on Lightning Protection (ICLP), 13-17 Sept. 2010, Cagliari, Italy
Link:https://doi.org/10.1109/ICLP.2010.7845756
Zugriffsart:campus
Institutes:FH Aachen / Fachbereich Energietechnik
collections:Verlag / IEEE