Objective: As high-field cardiac MRI (CMR) becomes more widespread the propensity of ECG to interference from electromagnetic fields (EMF) and to magneto-hydrodynamic (MHD) effects increases and with it the motivation for a CMR triggering alternative. This study explores the suitability of acoustic cardiac triggering (ACT) for left ventricular (LV) function assessment in healthy subjects (n=14). Methods: Quantitative analysis of 2D CINE steady-state free precession (SSFP) images was conducted to compare ACT’s performance with vector ECG (VCG). Endocardial border sharpness (EBS) was examined paralleled by quantitative LV function assessment. Results: Unlike VCG, ACT provided signal traces free of interference from EMF or MHD effects. In the case of correct Rwave recognition, VCG-triggered 2D CINE SSFP was immune to cardiac motion effects—even at 3.0 T. However, VCG-triggered 2D SSFP CINE imaging was prone to cardiac motion and EBS degradation if R-wave misregistration occurred. ACT-triggered acquisitions yielded LV parameters (end-diastolic volume (EDV), endsystolic volume (ESV), stroke volume (SV), ejection fraction (EF) and left ventricular mass (LVM)) comparable with those derived fromVCG-triggered acquisitions (1.5 T: ESVVCG=(56± 17) ml, EDVVCG=(151±32)ml, LVMVCG=(97±27) g, SVVCG=(94± 19)ml, EFVCG=(63±5)% cf. ESVACT= (56±18) ml, EDVACT=(147±36) ml, LVMACT=(102±29) g, SVACT=(91± 22) ml, EFACT=(62±6)%; 3.0 T: ESVVCG=(55±21) ml, EDVVCG=(151±32) ml, LVMVCG=(101±27) g, SVVCG=(96±15) ml, EFVCG=(65±7)% cf. ESVACT=(54±20) ml, EDVACT=(146±35) ml, LVMACT= (101±30) g, SVACT=(92±17) ml, EFACT=(64±6)%). Conclusions: ACT’s intrinsic insensitivity to interference from electromagnetic fields renders
Industrial facilities must be thoroughly designed to withstand seismic
actions as they exhibit an increased loss potential due to the possibly wideranging
damage consequences and the valuable process engineering equipment.
Past earthquakes showed the social and political consequences of seismic damage
to industrial facilities and sensitized the population and politicians worldwide
for the possible hazard emanating from industrial facilities. However, a holistic
approach for the seismic design of industrial facilities can presently neither be
found in national nor in international standards. The introduction of EN 1998-4
of the new generation of Eurocode 8 will improve the normative situation with
specific seismic design rules for silos, tanks and pipelines and secondary process
components. The article presents essential aspects of the seismic design of
industrial facilities based on the new generation of Eurocode 8 using the example
of tank structures and secondary process components. The interaction effects of
the process components with the primary structure are illustrated by means of
the experimental results of a shaking table test of a three story moment resisting
steel frame with different process components. Finally, an integrated approach of
digital plant models based on building information modelling (BIM) and structural
health monitoring (SHM) is presented, which provides not only a reliable
decision-making basis for operation, maintenance and repair but also an excellent
tool for rapid assessment of seismic damage.