Refine
Year of publication
Institute
Language
- English (39) (remove)
Document Type
- Article (23)
- Conference Proceeding (16)
Keywords
- Blitzschutz (6)
- Elektromagnetischer Schutzschild (3)
- Lightning (3)
- Direkter Blitzschlag (2)
- Erneuerbare Energien (2)
- Hybridsystem (2)
- Induzierte Spannungen (2)
- Lightning protection (2)
- Lightning protection system (2)
- Magnetische Felder (2)
- Risikoabwägung (2)
- electromagnetic shielding (2)
- reinforced concrete (2)
- Blitz (1)
- Blitzrisiko (1)
- Blitzschlag (1)
- Direct lightning strike (1)
- Elektromagnetische Kopplung (1)
- Industrieanlagen (1)
- Kalkulation (1)
- Kraftwerke (1)
- Lightning Protection (1)
- Lightning Risk (1)
- Maßstabsgetreues Modell (1)
- Photovoltaikanlage (1)
- Renewable energy (1)
- Risiko (1)
- Risk (1)
- Risk Assessment (1)
- Risk Management (1)
- Stahlbeton (1)
- Stahlbetonkonstruktion (1)
- Windenergieanlage (1)
- arresters (1)
- atmospheric modeling (1)
- calculations (1)
- conductors (1)
- current distribution (1)
- down-conductor (1)
- electromagnetic coupling (1)
- electromagnetic shield (1)
- hybrid system (1)
- hybrid-system (1)
- induced voltage (1)
- induced voltages (1)
- lightning (1)
- lightning flash (1)
- lightning protection (1)
- magnetic field (1)
- magnetic fields (1)
- metal façade (1)
- overvoltages (1)
- photovoltaic system (1)
- planning (1)
- power generation (1)
- power transmission lines (1)
- probability distribution (1)
- protection measures (1)
- renewable energy (1)
- risk assessment (1)
- scaled model (1)
- standards (1)
- steel columns (1)
- surges (1)
- touch voltage (1)
- wind turbine (1)
- Überspannung (1)
Lightning protection design of a renewable energy hybrid-system without power mains connection
(2001)
In the year 2000 a direct lightning strike to the hybridsystem without power mains connection VATALI on the Greek island Crete results in the destruction and damage of some mechanical and electrical components. The hybrid-system VATALI was not lightning protected at that time. The hardware damage costs are approx. 60,000 €. The exposed site of the hybrid-system on top of a mountain was and still is the reason for a high risk of lightning strikes. Also in the future further lightning strikes have to be taken into consideration. In the paper a fundamental lightning protection design concept for renewable energy hybrid-systems without power mains connection and protection measures against direct strikes and overvoltages are shown in detail. The design concept was realized exemplarily for the hybrid-system VATALI. The hardware costs for the protection measures were about 15,000 €. About 50% of the costs are due to protection measures against direct strikes, 50% are due to overvoltage protection. Future extensions, new installations, or modifications have to be included into the lightning protection design concept of the hybrid-system.
Large industrial facilities and power plants often require a huge number fo information and control cables between the differnet structures. These I&C-cables can be routed in reinforced concrete cable ducts or in isolated buried cable runs. KTA 2206 is the German lightning protection standard for nuclear power plants. During the last several years considerable effort has been made to revise this standard. Despite the well established principles and design guidelines for the construction of the lightning protection system, this standard puts special emphasis on the coupling of transient overvoltages to I&C-cables.
In the presented paper data collected from the field related to damage statistics of electrical and electronic apparatus in household are reported and investigated. These damages (total number approx. 74000 cases), registered by five German insurance companies in 2005 and 2006, were adviced by customers as caused by lightning overvoltages. With the use of stochastical methods it is possible, to reasses the collected data and to distinguish between cases, which are with high probability caused by lightning overvoltages, and those, which are not. If there was an indication for a direct strike, this case was excluded, so the focus was only on indirect lightning flashes, i.e. only flashes to ground near the structure and flashes to or nearby an incoming service line were investigated. The data from the field contain the location of damaged apparatus (residence of the policy holder) and the distances of the nearest cloud-to-ground stroke to the location of the damage registered by the German lightning location network BLIDS at the date of damage. The statistical data along with some complementary numerical simulations allow to verify the correspondence of the Standards rules used for IEC 62305-2 with the field data and to define some correction needs. The results could lead to a better understanding whether a damage reported to an insurance company is really caused by indirect lightning, or not.
Future evolution of risk management for structures : Advancement for the future IEC 62305-2 Ed3
(2011)
The 2nd edition of the lightning risk management
standard (IEC 62305-2) considers structures, which may
endanger environment. In these cases, the loss is not limited to
the structure itself, which is valid for usual structures. In the past
(Edition 1) this danger was simply taken into account by a special
hazard factor, multiplying the existing risk for the structure with
a number. Now, in the edition 2, we add to the risk for the
structure itself a “second risk” due to the losses outside the
structure. The losses outside can be treated independently from
what occurs inside. This is a major advantage to analyze the risk
for sensitive structures, like chemical plants, nuclear plants, or
structures containing explosives, etc. In this paper, the existing
procedure given by the European version EN 62305-2 Ed.2 is
further developed and applied to a few structures.
Risk management for structures with a risk of explosion should be considered very carefully when performing a risk analysis according to IEC 62305-2. In contrast to the 2006 edition of the standard, the 2010 edition describes the topic “Structures with a risk of explosion” in more detail. Moreover, in Germany separate procedures and parameters are defined for the risk analysis of structures with a risk of explosion (Supplement 3 of the German DIN EN 62305-2 standard). This paper describes the contents and the relevant calculations of this Supplement 3, together with a numerical example.
For typical cases of non-isolated lightning protection systems (LPS) the impulse currents are investigated which may flow through a human body directly touching a structural part of the LPS. Based on a basic LPS model with conventional down-conductors especially the cases of external and internal steel columns and metal façades are considered and compared. Numerical simulations of the line quantities voltages and currents in the time domain are performed with an equivalent circuit of the entire LPS.
As a result it can be stated that by increasing the number of conventional down-conductors and external steel columns the threat for a human being can indeed be reduced, but not down to an acceptable limit. In case of internal steel columns used as natural down-conductors the threat can be reduced sufficiently, depending on the low-resistive connection of the steel columns to the lightning equipotential bonding or the earth termination system, resp. If a metal façade is used the threat for human beings touching is usually very low, if the façade is sufficiently interconnected and multiply connected to the lightning equipotential bonding or the earth termination system, resp.
Large power plants can be endangered by lightning strikes with possible consequences regarding their safety and availability. A special scenario is a lightning strike to the HV overhead transmission line close to the power plant's connection to the power grid. If then additionally a so-called shielding failure of the overhead ground wire on top of the overhead transmission line is assumed, i.e. the lightning strikes directly into a phase conductor, this is an extreme electromagnetic disturbance. The paper deals with the numerical simulation of such a lightning strike and the consequences on the components of the power plant's auxiliary power network connected to different voltage levels.
Lightning safety guidelines
(2010)
This paper introduces lightning to the layman, noting the right behaviour in front of thunderstorms as well as protective measures against lightning. It also contributes to the prevention of lightning injuries and damages. This report was prepared by the authors inside the AHG1 Group for IEC TC81 (Lightning Protection).
Planning the air-terminations for a structure to be protected the use of the rolling-sphere method (electro-geometrical model) is the best way from the physics of lightning point-of-view. Therefore, international standards prefer this method. However, using the rolling-sphere method only results in possible point-of-strikes on a structure without giving information about the probability of strikes at the individual points compared to others.