The 2nd edition of the lightning risk management
standard (IEC 62305-2) considers structures, which may
endanger environment. In these cases, the loss is not limited to
the structure itself, which is valid for usual structures. In the past
(Edition 1) this danger was simply taken into account by a special
hazard factor, multiplying the existing risk for the structure with
a number. Now, in the edition 2, we add to the risk for the
structure itself a “second risk” due to the losses outside the
structure. The losses outside can be treated independently from
what occurs inside. This is a major advantage to analyze the risk
for sensitive structures, like chemical plants, nuclear plants, or
structures containing explosives, etc. In this paper, the existing
procedure given by the European version EN 62305-2 Ed.2 is
further developed and applied to a few structures.
Risk management for structures with a risk of explosion should be considered very carefully when performing a risk analysis according to IEC 62305-2. In contrast to the 2006 edition of the standard, the 2010 edition describes the topic “Structures with a risk of explosion” in more detail. Moreover, in Germany separate procedures and parameters are defined for the risk analysis of structures with a risk of explosion (Supplement 3 of the German DIN EN 62305-2 standard). This paper describes the contents and the relevant calculations of this Supplement 3, together with a numerical example.
For typical cases of non-isolated lightning protection systems (LPS) the impulse currents are investigated which may flow through a human body directly touching a structural part of the LPS. Based on a basic LPS model with conventional down-conductors especially the cases of external and internal steel columns and metal façades are considered and compared. Numerical simulations of the line quantities voltages and currents in the time domain are performed with an equivalent circuit of the entire LPS.
As a result it can be stated that by increasing the number of conventional down-conductors and external steel columns the threat for a human being can indeed be reduced, but not down to an acceptable limit. In case of internal steel columns used as natural down-conductors the threat can be reduced sufficiently, depending on the low-resistive connection of the steel columns to the lightning equipotential bonding or the earth termination system, resp. If a metal façade is used the threat for human beings touching is usually very low, if the façade is sufficiently interconnected and multiply connected to the lightning equipotential bonding or the earth termination system, resp.
Extrem hohe Blitzströme