Refine
Year of publication
Document Type
- Article (360)
- Conference Proceeding (177)
- Part of a Book (24)
- Book (8)
- Talk (3)
- Doctoral Thesis (2)
- Other (2)
- Master's Thesis (1)
- Poster (1)
- Report (1)
Language
- English (579) (remove)
Keywords
- Blitzschutz (6)
- Earthquake (5)
- Diversity Management (4)
- Energy storage (4)
- Power plants (4)
- Seismic design (4)
- Associated liquids (3)
- Concentrated solar power (3)
- Elektromagnetischer Schutzschild (3)
- Hybrid energy system (3)
- Lightning (3)
- Out-of-plane load (3)
- Seismic loading (3)
- earthquakes (3)
- Adjacent buildings (2)
- Central receiver power plant (2)
- Concentrated systems (2)
- Direkter Blitzschlag (2)
- Diversity (2)
- Electricity generation (2)
Institute
- Fachbereich Energietechnik (579) (remove)
For typical cases of non-isolated lightning
protection systems (LPS) the impulse currents are investigated which may flow through a human body directly touching a structural part of the LPS. Based on a basic LPS model with conventional down-conductors especially the cases of external and internal steel columns and metal façades are considered and compared. Numerical simulations of the line quantities voltages and currents in the time domain are performed with an equivalent circuit of the entire LPS.
As a result it can be stated that by increasing the number of conventional down-conductors and external steel columns the threat for a human being can indeed be reduced, but not down to an acceptable limit. In case of internal steel columns used as natural down-conductors the threat can be reduced sufficiently, depending on the low-resistive connection of the steel columns to the lightning equipotential bonding or the earth termination system, resp. If a metal façade is used the threat for human beings touching is usually very low, if the façade is sufficiently interconnected and multiply connected to the lightning equipotential bonding or the earth termination system, resp.
In the paper a lightning protection design concept for renewable energy hybrid-systems without power mains connection is described. Based on a risk analysis protection measures against direct strikes and overvoltages are shown in an overview. The design concept is realized exemplarily for the hybrid-system VATALI on the Greek island Crete. VATALI, not lightning protected at that time, was a victim of a lightning strike in the year 2000 causing destructions and damages of some mechanical and electrical components with costs of approx. 60.000 €. The hardware costs for the protection measures were about 15.000 €: about 50% of the costs are due to protection measures against direct strikes, 50% are due to overvoltage protection.
Lightning protection design of a renewable energy hybrid-system without power mains connection
(2001)
In the year 2000 a direct lightning strike to the hybridsystem without power mains connection VATALI on the Greek island Crete results in the destruction and damage of some mechanical and electrical components. The hybrid-system VATALI was not lightning protected at that time. The hardware damage costs are approx. 60,000 €. The exposed site of the hybrid-system on top of a mountain was and still is the reason for a high risk of lightning strikes. Also in the future further lightning strikes have to be taken into consideration. In the paper a fundamental lightning protection design concept for renewable energy hybrid-systems without power mains connection and protection measures against direct strikes and overvoltages are shown in detail. The design concept was realized exemplarily for the hybrid-system VATALI. The hardware costs for the protection measures were about 15,000 €. About 50% of the costs are due to protection measures against direct strikes, 50% are due to overvoltage protection. Future extensions, new installations, or modifications have to be included into the lightning protection design concept of the hybrid-system.
Lightning protection design of a renewable energy hybrid-system without power mains connection
(2001)
The longitudinal voltage of cable tubes with a screening mesh caused by partial lightning currents
(1989)
Comparison of single point and equipotential bonding for I&C systems of large-area industrial sites
(1994)