The 2nd edition of the lightning risk management
standard (IEC 62305-2) considers structures, which may
endanger environment. In these cases, the loss is not limited to
the structure itself, which is valid for usual structures. In the past
(Edition 1) this danger was simply taken into account by a special
hazard factor, multiplying the existing risk for the structure with
a number. Now, in the edition 2, we add to the risk for the
structure itself a “second risk” due to the losses outside the
structure. The losses outside can be treated independently from
what occurs inside. This is a major advantage to analyze the risk
for sensitive structures, like chemical plants, nuclear plants, or
structures containing explosives, etc. In this paper, the existing
procedure given by the European version EN 62305-2 Ed.2 is
further developed and applied to a few structures.
Risk management for structures with a risk of explosion should be considered very carefully when performing a risk analysis according to IEC 62305-2. In contrast to the 2006 edition of the standard, the 2010 edition describes the topic “Structures with a risk of explosion” in more detail. Moreover, in Germany separate procedures and parameters are defined for the risk analysis of structures with a risk of explosion (Supplement 3 of the German DIN EN 62305-2 standard). This paper describes the contents and the relevant calculations of this Supplement 3, together with a numerical example.
Seismic excited liquid filled tanks are subjected to extreme loading due to hydrodynamic pressures, which can lead to nonlinear stability failure of the thinwalled cylindrical tanks, as it is known from past earthquakes. A significant reduction of the seismically induced loads can be obtained by the application of base isolation systems, which have to be designed carefully with respect to the modified hydrodynamic behaviour of the tank in interaction with the liquid. For this reason a highly sophisticated fluid-structure interaction model has to be applied for a realistic simulation of the overall dynamic system. In the following, such a model is presented and compared with the results of simplified mathematical models for rigidly supported tanks. Finally, it is examined to what extent a simple mechanical model can represent the behaviour of a base isolated tank in case of seismic excitation